S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
65-0303—05
24
Warm Weather Shutdown 
Configuration
Table 14 displays Warm Weather Setpoint configuration 
parameters.
Demand Priority Configuration 
Parameters
Fig. 42 displays R7910A Hydronic Control Demand Priority 
configuration options. Press the arrows to change the priority 
order.
Fig. 42. Demand priority configuration.
Plate preheat 
setpoint
-40 °F to 266 °F (-40 °C to 130 °C)
Plate preheat on 
recognition time
___hour ___min ___sec
Plate preheat on 
hysteresis
-0 °F to 180 °F (-17 °C to 82 °C)
Plate preheat off 
hysteresis
-0 °F to 180 °F (-17 °C to 82 °C)
Plate preheat detect 
on threshold
-0 °F to 180 °F (-17 °C to 82 °C)
Plate preheat detect 
off threshold
-0 °F to 180 °F (-17 °C to 82 °C)
Plate preheat 
minimum on time
___hour ___min ___sec
Plate preheat delay 
after tap
___hour ___min ___sec
Table 13. DHW Plate Heat Exchanger 
Configuration Parameters. (Continued)
Parameter
Comment
Table 14. Warm Weather Setpoint 
Configuration Parameters. 
Parameter
Comment
Enable
Enabled, disabled
Setpoint
-40 °F to 266 °F (-40 °C to 130 °C)