S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
29
65-0303—05
T-Rise Limit Configuration 
Parameters
Table 22 displays T-Rise limit parameters.
Heat Exchanger High Limit 
Configuration Parameters
Table 23 displays T-Rise limit parameters.
Anti-Condensation Configuration 
Parameters (R7910A Hydronic 
Control Only)
Table 24 displays anti-condensation parameters. Use the left 
and right arrows to switch between Central Heat, Domestic Hot 
Water, Frost Protection, and Priority parameters.
Fig. 50. Anti-condensation configuration.
Table 22. T-Rise Limit Configuration Parameters.
Parameter Comment
Outlet T-rise enable
Enabled
Disabled
Heat exchanger T-
rise enable
Enabled
Disabled
T-rise degrees
0 °F to 234 °F (-17 °C to 112 °C)/sec
T-rise response
Recycle & delay
Recycle & delay with retry limit
Lockout
T-rise retry limit
0 to 100
T-rise delay
___hour ___min ___sec
Table 23. Heat Exchanger High Limit 
Configuration Parameters.
Parameter Comment
Heat exchanger high 
limit enable
Enabled
Disabled
Heat exchanger high 
limit setpoint
-40 °F to 266 °F (-40 °C to 130 °C)
Heat exchanger high 
limit response
Recycle & delay
Recycle & delay with retry limit
Lockout
Heat exchanger retry 
limit
0 to 100
Heat exchanger high 
limit delay
___hour ___min ___sec
Table 24. Anti-Condensation Configuration Parameters.
Parameter
Comment
CH Enable
Enabled
Disabled
CH Setpoint
-40 °F to 266 °F (-40 °C to 130 °C)
DHW Enable
Enabled
Disabled
DHW Setpoint
-40 °F to 266 °F (-40 °C to 130 °C)
Frost Protection 
Enable
Enabled
Disabled
Anticondensation 
Priority
Anticondensation is more important 
than (check those that apply):
Stack limit
Delta T limit
Slow start
Forced rate
Outlet high limit