S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
65-0303—05
30
Frost Protection Parameters 
(R7910A Hydronic Control Only)
Table 25 displays frost protection parameters.
Fig. 51. Frost Protection configuration.
Annunciation Configuration 
Parameters
Table 26 displays annunciation configuration parameters.
Fig. 52. Annunciation configuration example.
Safety Configuration Parameters
Table 27 through 30 display safety parameters.
NOTE: Login is required to change Safety Parameters and 
the SOLA Control will go to a Lockout 2 “waiting for 
safety data verification” when a change is made. 
Table 25. Frost Protection Configuration Parameters.
Parameter Comment
CH frost protection 
enable
Enabled
Disabled
DHW frost protection 
enable
Enabled
Disabled
Lead Lag frost 
protection enable
Enabled
Disabled
Outdoor frost 
protection setpoint
-40 °F to 266 °F (-40 °C to 130 °C) 
(applicable for CH only)
Lead Lag frost 
protection rate
___%
CH pump frost 
overrun time
___hour ___min ___sec
DHW pump frost 
overrun time
___hour ___min ___sec
Table 26. Annunciation Configuration Parameters.
Parameter Comment
Annunciation enable Enabled
Disabled
Annunciator (1–8) 
location
01 - Annunciator 1
02 - Annunciator 2
03 - Annunciator 3
04 - Annunciator 4
05 - Annunciator 5
06 - Annunciator 6
07 - Annunciator 7
08 - Annunciator 8
PII - Pre-Ignition ILK
LCI - Load Control Input
ILK - Interlock
Annunciator (1–8) 
short name
Up to 3 characters
Annunciator (1–8) 
name
Up to 20 characters