S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
65-0303—05
32
Fig. 56. Burner Control Flame Failure configuration.
Safety Parameter Verification
When any of the safety configuration parameters are changed, 
the safety parameter verification procedure must be performed 
before the control will resume burner control. The control 
enters a lockout state, if not already in one, and remains locked 
out until this verification procedure is performed.
Safety parameter verification lockout occurs when safety 
parameter setting is changed. See Fig. 57.
Fig. 57. Safety verification lockout.
The user must log in before verification can be completed, as 
Fig. 58. Safety verification login.
Table 29. Burner Control Ignition Configuration.
Parameter Comment
Pilot test hold
On
Off
Ignition source
Hot Surface Igniter
External ignition
Internal ignition
Pilot type
Direct burner constant ignition
Direct burner pulsed ignition
Intermittent
Interrupted
Lightoff rate
RPM or %
Preignition time
___hour ___min ___sec
Pilot Flame 
Establishing Period
15 secs
10 secs
4 secs
Igniter on during
1st half of PFEP
Pilot Flame Establishing Period
Main Flame 
Establishing Period
15 secs
10 secs
5 secs
Flame Threshold
μA/V
Table 30. Burner Control Flame 
Failure Configuration.
Parameter Comment
Ignite failure 
response
Lockout
Recycle
Recycle & hold
Recycle & lockout
Ignite failure delay
___hour ___min ___sec
Ignite failure retries
1, 3, or 5
MFEP flame failure 
response
Recycle
Lockout
Run flame failure 
response
Recycle
Lockout
Fan speed error 
response
Recycle
Lockout
Table 30. Burner Control Flame 
Failure Configuration. (Continued)