S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
41
65-0303—05
Hydronic Demand and Modulation 
Status
Table 49 displays the status page data for R7910A.
The bar graph displayed for this status is the outlet sensor 
temperature.
Fig. 80. Demand and Modulation Status menu (top).
Fig. 81. Demand and Modulation Status menu (bottom).
Inlet Temperature Status
Table 49 displays the status page data for R7910A inlet 
temperature.
The bar graph displayed for this status is the inlet sensor 
temperature.
Fig. 82. Inlet High Limit Status menu.
Fan Status
Table 50 displays the status page data for the fan in the control.
Table 48. Hydronic Demand and Modulation Status.
Data Comment 
Demand source
CH, DHW, Lead Lag, or Frost 
Protection (parameter that has current 
priority) 
Firing rate
% or RPM. Adjustable when firing rate 
control set to Manual. 
Demand rate
% or RPM.
Rate limiter
None, Outlet high limit, Delta T limit, 
Stack limit, Slow start limit, Anti-
condensation, Minimum modulation, 
Forced rate
Limited rate
% or RPM
Rate override
Burner control default, Burner control, 
manual firing rate off, None
Override rate
% or RPM
Table 49. Inlet High Limit Status.
Data Comment 
Inlet sensor state
None, Normal, Open, Shorted, 
Outside high range, Outside low 
range, Not reliable (None=no outlet 
sensor)
Inlet temperature 
Inlet sensor temperature (same as bar 
graph)