S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
65-0303—05
42
The bar graph displayed for this status is the fan speed.
Fig. 83. Control Fan Status menu.
Hydronic Pump Status
Table 51 displays the status page data for this example, 
Central Heat pump in the R7910A. Screens available for DHW, 
Boiler, System, Aux1 and Aux2 will be the same if that pump is 
configured.
Fig. 84. Hydronic CH pump status menu.
Flame Detection Status
The status data shown in Table 52 is displayed for flame 
detection in the R7910A or R7911.
The bar graph displayed for this status is the flame signal.
Fig. 85. Flame Detection Status menu.
NOTE: This same status is also displayed for burner control 
status. A separate status group is defined to provide a 
bar graph of the flame signal.
Table 50. Control Fan Status.
Data Comment 
Fan speed 
% or RPM (current fan speed) 
Maximum fan speed Setpoint of maximum fan speed (% or 
RPM) 
Minimum fan speed
Setpoint of minimum fan speed (% or 
RPM) 
Table 51. Hydronic CH Pump Status.
Data
Comment
CH Pump
On or Off
Controlling Pump 
Terminal
Pump A, B, or C
Status
On, Off, or Not Used
Delay time
Duration of delay time
Overrun time
Duration of overrun time
Frost overrun time
Duration of frost overrun time
Idle days
Number of days idle
Cycle count
Number of cycles
Table 52. Flame Detection Status.
Data Comment 
Flame detected
Yes or No 
Flame signal
Flame signal strength (same as bar 
graph)
Pilot test hold
Off or hold