S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
65-0303—05
44
Fig. 89. Lead Lag Slave Status menu.
Lead Lag Master Status - Hydronic 
Only
Table 56 shows the status page data for Lead Lag Master.
Fig. 90. Lead Lag Master Status menu.
R7910A OR R7911 
DIAGNOSTICS
The diagnostic page displays analog and digital I/O status of 
the control. The digital I/O data is displayed as LEDs that are 
either on (green) or off (red) (see Fig. 91–93). Not all digital I/O 
can be displayed at the same time on the page, so a horizontal 
scroll bar is used to move the view left and right to show all 
digital I/O data.
Fig. 91. Diagnostic digital I/O page (left).
Table 56. Lead Lag Master.
Data
Comment
Master enabled
Enabled
Status
normal
Demand source
Lead lag slave
Active Service
None
Off setpoint
160 °F (71 °C)
Setpoint
150 °F (66 °C)
On setpoint
145 °F (63 °C)
operating 
temperature
150 °F (66 °C)
Sensor state
normal
Sensor temperature
150 °F (66 °C)
Slave firing
no
Stager state
idle
Stager timer
CH demand
CH frost demand
no
DHW frost demand
no