Honeywell S7999B Manual De Usuario

Descargar
Página de 68
51
65-0303—05
• Setpoint (for corresponding demand source)
• Burner firing rate
• Hysteresis on (for corresponding demand source)
• Hysteresis off (for corresponding demand source)
The Clear button is disabled for the PID analysis (doesn’t apply to 
hysteresis).
The default sample rate is 15 sec periods (a tick mark on the X axis 
for every 15 second period, with minutes displayed every 4 tick 
marks).
Special case trend analysis graph for R7910/R7911 vessel heat 
exchange can be selected.
Fig. 112. Vessel analysis page.
Data included in the vessel analysis graph are:
• Outlet temperature
• Inlet temperature
• Heat exchange (outlet – inlet)
• Burner firing rate
Automatic sampling of trend data takes place when the trend 
analysis report is displayed. No user intervention is necessary to 
invoke sampling.
NOTE: Sample data is collected and stored in the S7999B. The 
R7910 or R7911 don’t collect any historical data for trending 
purposes. For this reason any S7999B reset causes all 
R7910 or R7911 sampling to start over with no data.
Trend analysis of the following data from each R7910/R7911 is 
possible:
Trend Analysis Snapshot
The trend analysis snapshot file is stored in Comma Separated Value 
(CSV) format in the S7999B so it can be imported into a spreadsheet 
program such as Microsoft Excel.
The trend analysis snapshot file can be viewed in graph form on the 
S7999B. It is also accessible in an Ethernet FTP session with the 
S7999B. This FTP session can be used to export the trend analysis 
snapshot file from the S7999B.
Diagnostics
Pressing the Diagnostics button permits some display hardware 
diagnostics (see Fig. 104). Normally, these diagnostics are 
applicable only for factory testing purposes, but conditions may 
arise that warrant this testing.
Fig. 113. Display diagnostics.
NOTE: COM 1 Communication test is a factory-only test. Perform-
ing this text when not connected to a factory test fixture will 
always yield a “Failed” result.
Each test is invoked by pressing the Test button next to the 
diagnostic. The results of the diagnostic test (“PASS” or “FAIL”) 
display in the text box next to the Test button.
Date and Time
Display time can be configured in the S7999B and S7999C OI 
Displays and applied to the R7910A or R7911. A date and time is 
entered by the user at the display and any data that is timestamped is 
marked with the current time and date in the display.
Table 59. R7910/R7911 Trend Analysis Data.
Data
Comment
Demand source
CH, DHW, LL (Lead Lag), or 
FP (Frost Protection) Steam 
Sensor
Outlet temperature (R7910 
only)
Firing rate
% or RPM
Fan speed
PWM feedback
Flame signal strength
V
Inlet temperature (R7910 
only)
If enabled
DHW temperature (R7910 
only)
If enabled
Outdoor temperature
If enabled
Stack temperature
If enabled
Header temperature (R7910 
only)
If enabled
CH setpoint
Actual CH setpoint based on 
time of day (TOD).
DHW setpoint (R7910 only)
Actual DHW setpoint based 
on TOD.
Central Heat Operation 
Analysis
Domestic Hot Water 
Operation Analysis (R7910 
only)
Vessel Analysis
Table 59. R7910/R7911 Trend Analysis Data. (Continued)
Data
Comment