S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
65-0303—05
52
The Display clock is set by selecting the Date and Time button 
on the Advanced Setup page. A screen similar to the following 
NOTE: It’s important that the time be set in the Display so 
correct timestamps are given to the R7910A or 
R7911 lockouts. The display’s time and date need 
to be set should power be interrupted to the dis-
play.
Fig. 114. Display Date and Time.
Edit the date and time and press the OK button to set the new 
settings. Press the Cancel button to exit without changing the 
time or date.
Version
Pressing the Version button on the Advanced Setup page 
displays manufacturer and software version information (Fig. 
Fig. 115. Code version—top view.
Fig. 116. Code Version—bottom view.
User Preferences
The User Preferences button displays General options as well 
as those for for COM1 and COM2.
Fig. 117. General tab.
The General tab (see Fig. 117) contains the following settings:
• Display alerts on Status Summary Bar? This determines 
whether non-safety alerts will be shown on the summary bar 
of the home page.
• Display empty parameter groups? This cleans up the 
home page by hiding unused parameter groups.
• Automatic synchronization with control when 
connections is made? This allows automatic display of 
new control to update when the connection is identified 
instead of manually making the synchronization when the 
operator is ready.
• Sound Audio Alarm for faults? This uses the display 
speaker to sound an alarm on shutdown for SOLA faults.
The COM1 tab (see Fig. 118) contains the following setting:
• Modbus address range 1-N: Sets the Modbus address for 
the connected device (range is 1 to 250).