Series 24 Minimum Piping Recommendations – Water Boiler
Recommendation 1
 is used  
when the load is constant and  
not varied due to mixing or 
multiple zones. Use when:
   system return water is not  
less than 135° F for  
prolonged periods of time
   system flow does not impact 
flow through the boiler
DRAIN VALVE
(SEE NOTE 4)
24-03 THRU 24-11 (W/20°F DROP)
24-03 THRU 24-12 (W/40°F DROP)
24-12 (W/20°F DROP)
DRAIN VALVE
(SEE NOTE 4)
REAR OF 
BOILER
REAR OF 
BOILER
3” x 12” NIPPLE
AND BELL REDUCER
(SEE NOTE 3)
SUPPLY
RETURN
2
RETURN
RETURN
HEADER
RETURN
BRANCH
2
2A
23 2
1
2B
1
SUPPLY
1
Recommendation 2
 is a primary-secondary piping method 
that maintains a constant flow through the boiler by using a 
secondary boiler circulator. This arrangement isolates the 
boiler from flow variations but does not safe-guard against 
cold return water temperatures. Use when:
   system return water is not less than 135° F  
for prolonged periods of time
   system flow does not impact flow through the  
boiler (i.e. zoning, mixing)
BOILER CIRCULATOR
(BY OTHERS - SEE NOTE 5)
DRAIN VALVE
(SEE NOTE 4)
SUPPLY
SYSTEM PUMP
CLOSELY
SPACED
TEES
MAX
4D
BOILER CIRCULATOR
(BY OTHERS - SEE NOTE 5)
DRAIN VALVE
(SEE NOTE 4)
SUPPLY
SYSTEM PUMP
CLOSELY
SPACED
TEES
MAX
4D
D
REAR OF 
BOILER
RETURN
3” x 12” NIPPLE
AND BELL REDUCER
(SEE NOTE 4)
REAR OF 
BOILER
RETURN
RETURN HEADER
RETURN BRANCH
2
2
2A
2B
1
23 2
1
24-03 THRU 24-11 (W/20°F DROP)
24-03 THRU 24-12 (W/40°F DROP)
24-12 (W/20°F DROP)
 
 
 
 RETURN PIPING SIZE (IN)
 
 
SUPPLY 
 
RETURN 
RETURN 
 
 
PIPING 
 
HEADER 
BRANCH 
 
 
SIZE (IN) (1) 
RETURN (2) 
(2A) 
(QTY.) SIZE (2B)
  BOILER 
20°F 
40°F 
20°F 
40°F 
20°F 
20°F 
   MODEL 
DROP 
DROP 
DROP 
DROP 
DROP 
DROP
 
24-03 
1-1/2 
1-1/2 
– 
– 
 
24-04 
1-1/2 
1-1/2 
– 
 
24-05 
1-1/2 
1-1/2 
– 
 
24-06 
2-1/2 
1-1/2 
2-1/2 
1-1/2 
– 
 
24-07 
2-1/2 
2-1/2 
– 
 
24-08 
2-1/2 
2-1/2 
– 
 
24-09 
– 
 
24-10 
2-1/2 
2-1/2 
– 
 
24-11 
2-1/2 
2-1/2 
– 
 
24-12 
2-1/2 
2-1/2 
(2) 3
Notes:
1.  All piping is schedule 40.
2.  Pipe sizes listed are based on a 20° F or 40°F differential (temperature drop).  
Select one to match application.
3.  When specified return piping is less than  3”, install 3” x 12” nipple and appropriate  
size bell reducer directly into boiler return tapping as shown.
4.  Drain valve—ball valve preferable, gate valve acceptable alternative  
(supplied by others).—Minimum valve size per ASME code is 3/4 ” NPT.
BOILER CIRCULATOR
(BY OTHERS - SEE NOTE 5)
DRAIN VALVE
(SEE NOTE 4)
SUPPLY
SYSTEM PUMP
CLOSELY
SPACED
TEES
MAX
4D
BOILER CIRCULATOR
(BY OTHERS - SEE NOTE 5)
DRAIN VALVE
(SEE NOTE 4)
SUPPLY
SYSTEM PUMP
CLOSELY
SPACED
TEES
MAX
4D
D
REAR OF 
BOILER
RETURN
3” x 12” NIPPLE
AND BELL REDUCER
(SEE NOTE 4)
REAR OF 
BOILER
RETURN
RETURN HEADER
RETURN BRANCH
2
2
2A
2B
1
23 2
1
24-03 THRU 24-11 (W/20°F DROP)
24-03 THRU 24-12 (W/40°F DROP)
24-12 (W/20°F DROP)
PIPE SIZING AND NOTES FOR RECOMMENDATIONS 1 AND 2