Installation & Operation Manual
11  
Maintenance   
Inspect ignition and flame 
sense electrodes
1.  Remove the ignition and both flame sense electrodes 
from the burner plate.
2.  Remove any deposits accumulated on the ignition/
flame sense electrodes using sandpaper.  If the 
electrodes cannot be cleaned satisfactorily, replace 
with new ones.
3.  Replace ignition/flame sense electrodes, making 
sure the gaskets are in good condition and correctly 
positioned.
Check ignition ground wiring
1.  Inspect boiler ground wire from the heat exchanger 
access cover to ground terminal strip.
2.  Verify all wiring is in good condition and securely 
attached.
3.  Check ground continuity of wiring using continuity 
meter.
4.  Replace ground wires if ground continuity is not 
satisfactory.
Check all boiler wiring
1.  Inspect all boiler wiring, making sure wires are in 
good condition and securely attached.
Check control settings
1.  Navigate to the Setup Screen and check all settings.  
See Section 1 of the Crest Service Manual.  Adjust 
settings if necessary.  See Section 1 of the Crest 
Service Manual for adjustment procedures.
2.  Check settings of external limit controls (if any) and 
adjust if necessary.
Perform start-up and checks
1.  Start boiler and perform checks and tests specified 
in Section 9 - Start-up.
2.  Verify cold fill pressure is correct and that operating 
pressure does not go too high.
Check burner flame
1.  Inspect flame through observation windows.
2.  If the flame is unsatisfactory at either high fire 
or low fire, remove and clean the burner.  Clean 
the burner thoroughly using a vacuum cleaner 
or compressed air.  Do not use compressed air to 
clean the burner if cleaning is performed inside a 
building.
 
• Shut down the boiler:
 
  
- Follow the “To Turn Off Gas to Appliance” instructions 
  
   for the boiler in Section 9 - Startup.
 
  
- Do not drain the boiler unless it will be exposed to 
  
  freezing temperatures.  If using freeze prevention fluid 
  
   in system, do not drain.
 
3.  Allow time for the boiler to cool to room temperature if it has 
been firing.
4.  Remove the top access panel to remove the gas/air manifold 
assembly.
5.  Remove the nuts securing the burner to the burner mounting 
plate.  Remove the burner (FIG. 11-2).
6.  When replacing the burner, ensure gaskets are in good condition 
and positioned correctly (FIG. 11-2).
7.  When securing the burner, be sure to tighten the nuts, but DO 
NOT over-tighten. Tighten the nuts to a torque setting of no 
more than 6.2 ft.-lbs.  When securing the burner mounting plate 
be sure to tighten the nuts, but DO NOT over-tighten.  Tighten 
the nuts to a torque setting of no more than 15.5 ft.-lbs.
BURNER
ASSEMBLY
MANIFOLD
GASKET
AIR/GAS
MANIFOLD
INSULATION
BURNER
GASKET
BURNER PLATE
FIBERBOARD
Figure 11-2 Burner Assembly
Check flame signal
1.  At high fire of each combustion system, the flame signal shown 
on the display should be at least 10 microamps.
2.  A lower flame signal may indicate a fouled or damaged flame 
sense electrode.  If cleaning the flame sense electrodes does 
not improve, ground wiring is in good condition, and ground 
continuity is satisfactory, replace the flame sense electrode.
3.  See Section 3 - Troubleshooting in the Crest Service Manual for 
other procedures to deal with low flame signal.