SMV 3000 Transmitter User’s Manual
33
4.5
Wiring SMV 3000 Transmitter,  
Continued
Wiring connections,
continued
Table 7
Wiring the Transmitter, Continued
Step
Action
3
Feed temperature sensor input leads through conduit entrance in
housing. Strip 1/4 inch (6.35 mm) of insulation from input leads.
If input is from …
Then…
2-wire RTD
connect RTD leads to 
terminals 1 and 3.
See Figure 15.
3-wire RTD 
connect RTD leads to 
terminals 1, 2, and 3.
See Figure 15.
4-wire RTD
connect RTD leads to 
terminals 1, 2, 3, and 4. See 
Figure 16.
2-wire Thermocouple
connect minus (–) lead to 
terminal 1 and plus (+) lead  to 
terminal 3. See Figure 16.
4
Feed loop power leads through conduit entrance on other side of
electronics housing opposite RTD wiring entrance.
ATTENTION   The transmitter accepts up to 16 AWG (1.5 mm
diameter) wire.
5
Strip 1/4 inch (6.35 mm) of insulation from leads. Observing polarity,
connect positive loop power lead to SIGNAL + terminal and negative
loop power lead to SIGNAL – terminal.
Example - Connecting loop power to transmitter.
+
_
Loop 
Power
TEST
SIG
+
+
METER L
SIGNAL
1
2
TC
3
4
+
+
6
If you have an optional analog meter, be sure jumper strap is removed
from across METER terminals, yellow lead from meter is connected to
METER – terminal and red lead is connected to METER + terminal.
See control drawing 51404251 (for intrinsically safe installations)  or
wiring diagram 51404250 (non-intrinsically safe) included in Section 13.
Continued on next page