If the flame flutters or is blown out, combustion products are escaping 
from the relief opening. If this occurs, do not operate the water heater 
until proper adjustments or repairs are made to the vent pipe system 
and/or air supply requirements.
Checking the Draft
WARNING
Burn Hazard
Do not touch vent.
Doing so can result in burns.
 
After successfully lighting the water heater, allow the unit to 
operate for 15 minutes and check the draft hood relief opening 
for proper draft (Figure 30). Make sure all other appliances in the 
area are operating and all doors/windows are closed when 
performing the draft test. Pass a match flame or smoke around 
the relief opening of the draft hood. A steady flame or smoke 
drawn into the opening indicates proper draft.
Water Heater Operation
Figure 29 below shows the water heater’s sequence of operation 
when a call for heat is initiated. The ignition control module will 
attempt to light the burner three times. If the ignition control does 
not detect ignition it will enter lockout mode, indicated by display 
flashing status code (see status code 3 page 38 and/or status 
code 8 page 39).
Flue Products Vented 
to Ouside of Building
Draft Hood
Dilution Air 
Air is drawn in for
combustion. Keep 
area clean and free 
from combustibles 
and flammable vapors.
The water heater must be installed according to all local and state 
codes or in the adsence of local and state codes, the “National Fuel 
Code”’ ANSI Z223.1(NFPA 54)- current edition.
Dilution Air 
(Relief Opening)
Dilution Air 
Match
Outer Door
Floor Drain
6” Maximum 
Air Gap
FIGURE 30.
FIGURE 29.
SEQUENCE OF OPERATION
System will verify pressure 
switch operation and start a 
5 second pre-purge, then air 
intake fan will turn off.
Ignitor will start a 12 second 
warm up period. “IGN” will 
show on display.
Gas valve/thermostat is de- 
energized and air intake fan 
continues for a post purge time 
of approximately 5 seconds.
Water heater returns to standby 
mode.
Main burner flame is detected by 
flame sense rod. Air intake fan 
and main burner will continue to 
operate until water temperature 
inside the tank reaches 
temperature set point.
Gas valve/thermostat will do a 
relay check (relay clicks will be 
heard).
Display will show temperature 
set point during call for heat.
Gas valve/thermostat will open 
for 4 second trial for ignition 
and fan will turn on.
Call for heat indicated by 
flashing of display screen 
status codes.
Draft Blower is energized.