ZIO
®
/ZIO PLUS LCD WALL MODULES
63-2719—03
4
SAVE BUTTON
A SAVE button is available on screens that allow entries or 
selections. It is enabled whenever any change is made on the 
screen, and allows you to save your selections/entries at any 
time. See the ROOMSP Details area of the Categories and 
Parameters window in Fig. 12 on page 7 for an example of the 
SAVE button.
Save is enabled whenever a change is made to the current 
page. When you press the SAVE button, the preview screen 
displays and your changes are reflected in the preview.
If you try to leave the current screen without saving (click 
another icon or press the Back or Next button) and have made 
changes, a warning message appears.
Memory Usage
The wall module has a fixed amount of memory available for 
configuration data. The TR70 has 1,020 bytes of memory, the 
TR71 has 2,000 bytes of memory, and the TR75 has 4,950 
bytes of memory. To view the current memory use information 
click on the Memory Usage Details button. A new window 
opens and displays a bar graph indicating the percentage of 
current memory used in each memory category.
Each of the memory categories should be below 100%. See 
NOTE: For a single Zio memory usage must be equal to or 
less than 100% in order to download the configura-
tion to the programmable controller. If using multiple 
Zios, you should also check the Spyder Resource 
usage. Total Zio memory use is limited to 5K bytes 
on Spyder.
View the online help in the WEBs-AX Workbench to see 
troubleshooting tips for reducing memory usage in the TR70 
Series if memory use is above 100%.
The following warning message displays when the memory 
usage is greater than 100%:
“Warning: Memory Limit Exceeded. The current wall 
module configuration requires more memory than the wall 
module model can support. You will need to change the 
configuration so that the memory usage is 100% or less 
before pressing the FINISH button.”
Fig. 4. Memory Usage Details screen.
Wall Module Configuration
To begin configuring the wall module: 
1. Right click on the configuration’s function block to open 
the Configuration Properties menu.
2. Left click on Configure Properties. The Configuration 
Wizard opens. The Configuration Wizard steps (see Fig. 
5) are used to configure the wall module. 
Fig. 5. Wall Module - Configuration Wizard window showing 
Menu selections only.