General Settings
Using Fig. 6 and Table 4 as a guide, configure the General 
Settings. An image of the selected model and its capabilities 
updates in the display at the bottom of the window.
Fig. 6. General Settings screen.
If you are creating a customized configuration or modifying a 
pre-programmed configuration, continue with “Categories and 
If you are using a pre-programmed configuration as is, 
Categories and Parameters
I
 Categories 
and 
Parameters selection from 
Wizard Menu
The categories and parameters menu item allows you to 
create, edit, and delete categories and parameters.
ADDING A CATEGORY
Fig. 7 shows the categories listed in tree format in the main 
window where you can add, edit, or remove them. In the 
bottom pane, Category Preview (at the bottom of Fig. 7
shows the current selected item. 
Clicking the Add Category button displays a details pane 
below the category and parameter tree as shown in Fig. 8.
NOTE: You can use the Remove button to delete unused 
categories and parameters to free up memory 
space.
Fig. 7. Category Preview.
CATEGORY DETAILS
When you select a category from the Categories tree list and 
click the Edit button, a details pane displays for that category 
Here you can enter a category name and description. The 
number of parameters in this category are shown. The 
description text you enter is loaded to the controller but cannot 
be seen in the preview.
Table 4. General Settings.
Item
Function/Use
Block Name
The wizard displays S-Bus Wall Module.
Wall Module
Type
Select the appropriate type (Temperature 
Only, or a combination of Temperature, 
and/or Humidity) from the drop down list.
Model Options
Click LCD Display.
Select Model
Select the appropriate model, TR70, 
TR71, or TR75, from the drop down list.
Wall Module
Address
Select a unique address for each TR70 
Series devices connected to the Spyder. 
TR70 can be set from 1-5 and TR71/
TR75s can be set from 1-10. The 
address selected must match the 
address setting at the wall module (using 
the rotary switches). If setting the TR71/
TR75 rotary switch to 0, set the address 
to 10 in the configuration tool.
Time Display
Format
Select 12 or 24 hour format.