Bradford-White Corp BWCH Manual De Usuario

Descargar
Página de 64
Page 25
COPPER BRUTE II (500 - 2000)
Figure 14. Field Wiring Panel
Figure 15. External Control Connection Wiring.
with the Copper Brute II is installed in the piping 
or tank, per the suggested piping diagrams, and 
connected to the “S C2” and “SUP S” terminals. See 
Section 6.3
 for “Mode” definitions and 
Figures 22 to 
24
 for field wiring schematics.
Outdoor Reset Sensor: The outdoor reset 
sensor, if used, is connected to the “OD S” and “S C2” 
terminals.
Field Installed Pump: A pump contactor can 
be wired to the “PMP” and “PMP” terminals (these 
terminals supply 24VAC to close the contactor 
whenever the boiler pump would be operated). 
NOTE: In some cases, the boiler pump is operated 
continuously.
External Alarm
: An external power supply and 
alarm can be connected to the “ALRM” and “ALRM” 
terminals. In the event of an ignition system lockout, a 
contact closure occurs across these terminals.
External Heat Demand Indication
: 24VAC 
is present across the “HT OUT” and “LWCO GND” 
terminals whenever the temperature control sees a 
system heat demand. This can be used to power a 
contactor (0.5 Amp, maximum) for devices operated 
whenever the boiler could fire (combustion air fans, 
motorized louvers, etc.) NOTE: In some cases, the 
temperature control will always see a heat demand 
in the system, such as when the “Ht D” and Com D” 
terminals are jumpered.
Other Field Interlocks
: To install other field-
wired devices to interlock with the boiler (louver 
switches, flow switches, etc.), remove the jumper 
between the “COM” and “NO” terminals and wire the 
device in series across these terminals. (See 
Section 
5.3
 for important information about external staging 
controls and building automation systems.)
System Heat Demand
: Remove the jumper 
across the “COM D” and “Ht D” terminals, and con-
nect the zone pump or valve end switch, thermostat, 
aquastat, or other indication of system heat demand 
to these terminals. If no indication of a system heat 
demand will be provided, the jumper must remain in 
place. When jumpered, the temperature control will 
always see a heat demand, and the Copper Brute II 
pump (if equipped) or any pump with its contactor 
connected to the “PMP” and “PMP” terminals will 
run continuously. In addition, any device connected 
through the “HT OUT” and “LWCO GND” terminals 
for an external indication of the heat demand will 
run continuously. See 
Section 6
 for more information 
on the system heat demand for various modes of 
operation.
Refer to 
Figures 22 through 24
 for field wiring of