APPLICATION 
MODE 
SYSTEM
 
 
SETTING 
SENSORS USED 
• Parallel piping (non-
  primary/secondary) 
  hydronic system 
• None
• DHW with or without
  a tank aquastat
• Primary/secondary 
  hydronic system 
• Bradford White System
  (pref'd by Bradford White) 
 
  Sensor (shipped
• No outdoor reset 
 
  with each Copper Brute II)
• Parallel piping (non-
  primary/secondary) 
  hydronic system 
• Bradford White System
• DHW 
 
 
  Sensor (shipped (with
• Advanced control  
 
  each Copper Brute II)
 capability
• No outdoor reset
• Parallel piping (non-reset 
 
• Bradford White outdoor
  primary/secondary) 
 
  sensor (optional
  hydronic system 
  part #R2014000)
• Advanced control 
 
 
  capability  
 
• Outdoor reset 
 
 
• Primary/secondary 
 
• Bradford White System
  hydronic system 
  Sensor (shipped
  (preferred by 
 
  with each
     Bradford White) 
 
  Copper Brute II)
• Outdoor reset 
 
• Bradford White outdoor  
   
 
 
   reset sensor (optional part
   
 
 
  # R2014000)
• Building automation
 control
• Multiple boiler system 
• None
 control
• Energy management
 system
• Other external control
Table 11. Modes and Sensors for Applications.
contact the factory.
There are three black programming buttons on 
the Temperature Control (see 
Figure 25
). Press and 
hold all three programming buttons until the word 
ADJUST appears in the upper right corner of the LCD 
display (it replaces the word 
VIEW).
Pressing 
ITEM
 cycles you through the items you 
need to program. 
UP ARROW
 increases the value of 
that item, while 
DOWN ARROW
 decreases it. ADJUST 
mode exits if you don’t press a button for 20 seconds. 
To return to 
ADJUST mode, simply press and hold the 
three buttons again.
The first item is MODE; enter the mode number 
as determined above. The Temperature Control will 
then present you with some or all of the following 
options, depending on the mode you have chosen:
In mode 6 (external boiler control), you will not 
see the following options. Refer to 
Section 6.4.10
 for 
setup information for mode 6.
 
FOR ALL OTHER MODES:
BOIL MASS (Boiler Mass): Always choose “1”.
BOIL TARGET (Boiler Target Temperature): 
Your desired set-point temperature. See 
Section 6.4.5
 
and 
Figure 26
 for more information.
BOIL MIN (Boiler Minimum Temperature): This 
setting tells the Temperature Control to maintain at 
least this temperature, even if the PID logic determines 
a lower setting would save energy. The BOIL MIN 
should always be 120°F (49°C) or higher to prevent 
condensation, and can be set up to 10°F below your 
BOIL TARGET temperature. See 
Section 6.4.3
 for 
more information.
BOIL MAX (Boiler Maximum Temperature): 
This setting tells the Temperature Control to limit the 
maximum outlet temperature to this setting or below, 
and determines how quickly the temperature control 
“stages down” or off. If the BOIL MAX setting is 
much higher than the BOIL TARGET temperature, the 
temperature control will fire all stages until the target 
temperature is reached, and then shut down all stages 
at once. To enable gradual staging down of the boiler 
as you approach your target temperature, set the BOIL 
MAX to the same setting as the target temperature. See 
Section 6.4.4
 for more information.
DIFF 
(Boiler Differential): This setting is divided 
above and below the target temperature. The water 
will be allowed to cool ½ this setting below the target 
temperature before first stage fires, and will heat to ½ 
this setting above the target temperature before staging 
the boiler down. See 
Section 6.4.1
 and 
Figure 28
 for 
more information.
PUMP DLY (Pump Delay): On pump mounted 
units, the boiler mounted pump continues to run for 
the time selected after the heat demand in the system is 
satisfied. This setting also affects the 24VAC output on 
the “PMP” “PMP” terminals (see 
Section 5.2
). These 
terminals can power a contactor for a larger system 
pump. Bradford White recommends a minimum pump 
Figure 25. Temperature Control.