Bradford-White Corp BWCH Manual De Usuario

Descargar
Página de 64
Page 39
COPPER BRUTE II (500 - 2000)
Figure 27.  Temperature Control Target Temperature  
 
Graph.
delay setting of 5 minutes. See 
Section 6.4.6
 for more 
information. 
NOTE:
 In modes other than mode 6, the pump will 
run continuously if the “HtD” and “ComD” terminals 
are jumpered and not connected to a zone valve or 
pump end switch, or other “contact closure” device 
to indicate when the heat demand in the system is 
satisfied. The pump will never run, and the boiler will 
never fire, if the jumper is removed and the terminals 
left empty.
OUTDOOR RESET (modes 4 and 5): Outdoor 
reset adjusts the target temperature based on the 
outdoor air temperature and reset ratio. The reset ratio 
is determined from the Boiler Start, Boiler Design, 
Outdoor Start and Outdoor Design settings.
HEAT DEMAND – For heat demand to exist, 
there must be continuity between the Com D (common 
demand) and Ht D (heat demand) terminals. The 
Copper Brute II ships with a jumper between these 
terminals. 
The control also evaluates the sensor(s) installed 
in the system. If the control is not in warm weather 
shutdown (WWSD), and the sensor(s) are below the 
target temperature, the “Dem” segment is turned on in 
the display. The control energizes the pump (on pump 
mounted boilers) and energizes both “PMP” terminals. 
The pump symbol appears in the display (see 
Figures 
25 and 26).
 The control then operates the stages to 
maintain the setpoint temperature.
Boil Start
 (Boiler Start): The BOIL START 
temperature is the theoretical boiler supply 
temperature that the heating system requires when the 
outdoor air temperature equals the OUTDR START 
temperature setting. 
EXAMPLE 1
DHW (Mode 3) Programming. 
For domestic 
hot water systems up to 175°F / 79°C, use mode 3 as 
described below. 
Step 1: Install the additional sensor into the 
storage tank, wiring it to “SC2” and “SUPS” terminals 
on the field wiring panel (
Figure 23
).
Step 2: 
Press the three programming buttons 
to enter 
ADJUST mode (
Figure 25
). Press ITEM to 
select the programming item, and the arrow keys to 
adjust the setting. TARGET TANK is desired tank 
temperature. Recommended settings with a desired 
tank temperature of 125°F:
Example DHW Programming
Item F° 
MODE 
3
BOIL TARGET 
140°F 
60°C
TARGET TANK 
125°F 
52°C
DIFF TANK 
2°F 
1°C
BOIL MASS 
1
DIFF 
2°F 
1°C
DLY 
5:00 
5:00
F° 
F° 
°C
Step 4: 
See 
Section 6.4.11 Limit Controls.
 
Set both high limits 25°F / 14°C higher than BOIL 
TARGET to allow for temperature rise across heat 
exchanger. Manual high limits on water heaters have 
a maximum 200°F / 93°C setting. (If water must be 
at 175°F / 79°C or higher with a volume water heater 
model, use mode 1. For volume water applications 
exceeding 200°F / 93°C, contact the factory.)
Fine tuning:
 For faster staging, increase BOIL 
TARGET setting. Larger DIFF TANK and DIFF 
settings will slow response to demand, but may save 
energy. 
If unit short cycles, enter Advanced 
Programming mode (
Section 6.4
) and increase 
BOILER MAX setting to the BOIL TARGET setting 
or higher. Set BOILER MIN to 120°F / 49°C, and 
STGMODE to PID. See 
Section 6.4.12
 Advanced 
Programming Mode
 to enter Advanced Programming 
mode, or contact the factory for assistance.
EXAMPLE 2
Hydronic Primary/Secondary (Mode 2) 
Figure 26. Temperature Control Symbol Description.