the typical coldest temperature of the year where the 
building is located. This temperature is used when 
doing heat loss calculations for the building.
Boiler Design (
BOIL DSGN– The BOIL 
DSGN temperature is the water temperature required 
to heat the boiler zones when the outdoor air is as cold 
as the OUTDR DSGN temperature.
Warm Weather Shut Down (WWSD
– When 
the outdoor air temperature rises above the WWSD 
setting, the control turns on the WWSD segment 
in the display. When the control is in WWSD, 
the Dem segment is displayed if there is a heat 
demand. However, the control does not operate the 
heating system to satisfy this demand. The control 
does respond to a setpoint demand and operates as 
described in the Reset Override section (next).
Reset Override (
SETPOINT DEMAND– This 
is used when override of the outdoor reset curve is 
needed, such as when an indirect water heater is served 
by the heating system. A setpoint demand is required 
whenever heat is required for the setpoint load. The 
setpoint demand overrides the reset water temperature. 
The control turns on the Setp Dem pointer in the 
display. The control energizes the pump (on pump-
mounted boilers), energizes the Pmp-Pmp terminals, 
and turns on the boiler pump segment in the display.