Bradford-White Corp BWCH Manual De Usuario

Descargar
Página de 64
Page 46
 
B
RADFORD
 W
HITE
 C
ORP.
The control then operates the boiler stages to maintain 
the programmed boiler target temperature. The reset 
override operation is not affected by WWSD.
6.4.10 External Boiler Operation
When mode 6 is selected, the control allows for 
an external control to operate the Copper Brute II’s 
stages. In this mode, the control operates the pump in 
order to provide purging and exercising. The staging 
operation is provided by an external device such as 
an Energy Management System (EMS) or External 
Staging Control.
Heat Demand 
– A heat demand is generated 
when stage one is wired properly, and the external 
control closes the contacts on the stage one terminals 
(1C-1NO), calling the Copper Brute II for heat. The 
Copper Brute II is shipped with a jumper between 
the Com D and Ht D terminals, and this jumper must 
remain in place when and external control is providing 
the heat demand signal to these terminals. The control 
energizes the boiler pump (if equipped), energizes 
the Pmp-Pmp terminals, and turns on the boiler pump 
segment in the display. The control also turns on 
stage 1 of the boiler. 
Section 5.3
 contains important 
information about external staging controls and 
building automation systems. Other wiring methods 
may be unsafe. The wiring in 
Section 5.3
 of this 
manual must be used.
6.4.11 Limit Controls
In addition to the temperature control, Copper 
Brute II appliances are fitted with a manual reset 
high limit and an automatic reset high limit. These 
are located near the rear of the cabinet on the right 
side, behind the slide out drawer (see 
Figure 32
). 
Both controls should be set at least 25°F higher than 
the target temperature to avoid short cycling. To set 
these controls, remove the control panel cover and 
pull the control panel out to gain access. Appliances 
with reversed heat exchangers have the limit controls 
relocated to the left side of the appliance. The left 
access door must be removed to gain access to the 
limit controls on these appliances.
6.4.12 Advanced Programming Mode
Advanced programming mode allows the 
installer to set the temperature control for proportional 
staging. In advanced programming mode, the 
interstage differential, interstage delay, interstage on 
and off delay, and minimum time on and off are all set 
manually.
NOTE:
 Advanced programming mode is rarely 
required. It is intended for advanced installers, 
and only when the application demands such 
programming.
To enter advanced programming mode, remove 
the bezel on the temperature control by pulling out at 
the bottom. Remove the small phillips head screw to 
access the dip switch. The dip switch is mounted on a 
circuit board. 
Locate the letter “A” on the circuit board and 
slide the corresponding dip switch toward the letter 
“A”. The default setting of this dip switch is toward 
the 
OFF
 lettering on the circuit board.
6.5  Operating the Burner and Set Up
6.5.1  Set Up for 0 to 2500 Feet Altitude
The Copper Brute II appliance utilizes a modular 
design to achieve its stage-firing. The setup must be 
checked before the unit is put in operation. Problems 
such as failure to start, rough ignition, strong exhaust 
odors, etc. can be due to improper setup. Damage to 
the Copper Brute II resulting from improper setup is 
not covered by the limited warranty.
1.  Using this manual, make sure the installation 
is complete and fully in compliance with the 
instructions.
2.  Determine that the appliance and system are 
filled with water and all air has been bled from 
both. Open all valves.
3.  Observe all warnings on the Operating 
Instructions label and turn on gas and electrical 
power to appliance.
4.  Switch on the appliance power switch located on 
the right side of the unit.
5.  The Copper Brute II will enter the start sequence, 
as long as the unit is being called for heat. The 
blower and pump come on for pre-purge, then 
the ignitor warm-up sequence starts and after 
the ignitor warm-up is complete and all safety 
devices are verified, the gas valves open. If 
ignition doesn’t occur, check that there is proper 
gas supply. Wait 5 minutes and start the unit 
again. During initial start up, air in the gas line 
may cause the Copper Brute II to "lock out" 
during the first few trials for ignition. Depending 
on the ignition modules installed, the manual 
reset button on the ignition modules may need to 
be depressed to restart the Copper Brute II.
6.  When the unit is running, the supply gas pressure 
must be checked. Inlet gas pressure must not 
exceed 13" w.c. (3.2kPa). The minimum inlet gas 
pressure is 5" w.c. (1.2kPa).
7.  Once the inlet gas pressure is verified, the 
outlet gas pressure from each valve (manifold 
gas pressure) must be checked, and adjusted, if 
necessary. The manifold gas pressure must be 
2.5" w.c. (0.62kPa).
8.  Complete the setup by checking the CO
2
 at the 
outlet of the unit. The CO
2
 should be 8% for 
natural gas, or 9.2% for propane.
9. 
After placing the appliance in operation, the 
Burner Safety Shutoff Device must be tested
To test: 
 
(a)  Close gas shutoff valve with burner 
operating.