Venting system
examine the venting system every six months for obstructions 
and/or  deterioration  of  the  vent  piping.  Check  all  vent  system 
connections for leakage and repair or reseal as necessary.
remove all soot or other obstructions from chimney which will 
retard free draft.
intake air sCreen
The intake air screen is attached to the inlet end of the combustion 
blower. Inspect the intake air screen every six months. The intake air 
screen should be cleaned of any buildup of debris or foreign material.
temperature-pressure relief ValVe test
•  Burn hazard.
•  Hot water discharge.
•  Keep clear of Temperature- 
Pressure Relief Valve 
discharge outlet.
It is recommended that the Temperature-Pressure relief Valve 
should  be  checked  to  ensure  that  it  is  in  operating  condition 
every 6 months.
When checking the Temperature-Pressure relief Valve operation, 
make sure that (1) no one is in front of or around the outlet of the 
Temperature-Pressure relief Valve discharge line, and (2) that 
the water discharge will not cause any property damage, as the 
water may be extremely hot. Use care when operating valve as 
the valve may be hot.
To  check  the  relief  valve,  lift  the  lever  at  the  end  of  the  valve 
several times, see Figure 25. The valve should seat properly and 
operate freely.
If after manually operating the valve, it fails to completely reset and 
continues to release water, immediately close the cold water inlet 
to the water heater and drain the water heater, see Draining and 
Flushing on page 29. replace the Temperature-Pressure relief 
Valve  with  a  properly  rated/sized  new  one,  see  Temperature-
Pressure  relief  Valve  on  pages  13-14  for  instructions  on 
replacement.
figure 25.
If  the  Temperature-Pressure  relief  Valve  on  the  water  heater 
weeps  or  discharges  periodically,  this  may  be  due  to  thermal 
expansion.
nOTe: excessive water pressure is the most common cause of 
Temperature-Pressure  relief  Valve  leakage.  excessive  water 
system pressure is most often caused by "thermal expansion" 
in a "closed system." See Closed Water Systems and Thermal 
expansion on page 13. The Temperature-Pressure relief Valve 
is not intended for the constant relief of thermal expansion.
Temperature-Pressure relief Valve leakage due to pressure build 
up in a closed system that does not have a thermal expansion 
tank installed is not covered under the limited warranty. Thermal 
expansion tanks must be installed on all closed water systems.
DO  nOT  PlUG  THe  TeMPerATUre-PreSSUre  relIeF 
VAlVe  OPenInG. THIS  CAn  CAUSe  PrOPerTY  DAMAGe, 
SerIOUS InJUrY Or DeATH.
explosion hazard
Temperature-Pressure relief Valve
must comply with AnSI Z21.22-
CSA 4.4 and ASMe code.
Properly sized temperature-
pressure relief valve must be
installed in opening provided.
Can result in overheating and
excessive tank pressure.
Can cause serious injury or death.
anode rod inspeCtion
The anode rod is used to protect the tank from corrosion. Most 
hot water tanks are equipped with an anode rod. The submerged 
rod sacrifices itself to protect the tank. Instead of corroding tank, 
water ions attack and eat away the anode rod. This does not affect 
water’s taste or color. The rod must be maintained to keep tank 
in operating condition.
Anode deterioration depends on water conductivity, not necessarily 
water  condition. A  corroded  or  pitted  anode  rod  indicates  high 
water conductivity and should be checked and/or replaced more 
often than  an anode rod that appears to be intact. replacement 
of a depleted anode rod can extend the life of your water heater. 
Inspection should be conducted by a qualified technician, and at 
a minimum should be checked annually after the warranty period.
Artificially softened water is exceedingly corrosive because the 
process substitutes sodium ions for magnesium and calcium ions.
The use of a water softener may decrease the life of the water 
heater tank.
The anode rod should be inspected after a maximum of three 
years  and  annually  thereafter  until  the  condition  of  the  anode 
rod dictates its replacement. Anode replacement is not covered 
by warranty.
nOTe: Artificially softened water requires the anode rod to be 
inspected annually.
maintenanCe