EQUIREMENTS
Power requirements: 115-Volts AC power, 15-Amp service 
receptacles, type N5/15 or NEMA 5-15R (for U.S.) or 220 Volts AC for 
Europe.
Thermal Recom-
mendations 
This sections contains recommendations for handling the heat generated 
by the CoreBuilder 7000 family ATM switch. It is essential that you 
provide a suitable environment for both performance and safety.
General
Recommendations
The following are some general thermal recommendations for the wiring 
closet:
Ensure that the ventilation in the wiring closet is adequate to maintain 
a temperature below 40° C (104° F).
During non-business hours, make sure that the ventilation is not shut 
down while a CoreBuilder 7000 family ATM switch remains powered 
up; otherwise, the equipment may overheat.
Power and Heat
Specifications
The following are power and heat specifications for the CoreBuilder 7000 
family ATM switch:
Maximum power consumption: 250 Watts
Maximum heat generated: 1724 BTU per hour
Operating temperature: 0° to 40° C (32° to 104° F)
Wiring Closet 
Considerations 
The cabling system used at the facility should cover the majority of wiring 
closet concerns. You may want to consider the following 
recommendations.
Verify that the facility meets all requirements mentioned in the system 
cabling plan.
Ensure that the system is easily accessible for installation and service.
Use AC power, 15-Amp service receptacles, type N5/15 or NEMA 
5-15R for 120Vac.
Select a vinyl floor covering for the wiring closet. (Concrete floors tend 
to accumulate dust, and carpets often cause static electricity.)
Ensure that the wiring closet floor is flat and level. If the floor is not 
level, ensure that the racks are bolted to the floor to prevent them 
from tipping over.