Distribution Rack Requirements
C-3
Ensure that all wiring closets have doors with locks to prevent 
unauthorized access.
Provide adequate overhead lighting in the wiring closet for easy 
maintenance.
Ensure that each wiring closet has a suitable ground. All metal racks, 
enclosures, boxes, and raceways in the closet should be grounded.
Assign wiring closet identification numbers using architectural 
location codes or some type of floor grid matrix.
Ensure that all system environmental requirements are met (such as 
ambient temperature and humidity).
Distribution Rack 
Requirements 
This section describes the basic mechanical and space requirements for 
the distribution rack (refer to Figure C-1).
Figure C-1   Distribution racks
Mechanical
Requirements
Racks should comply with the standards and requirements mentioned in 
the cabling system plan and should conform to conventional standards. 
In the United States, use EIA Standard RS-310C: Racks, Panels, and 
Associated Equipment. In countries other than the United States, use IEC 
Standard 297: Dimensions of Panels and Racks.
The following are distribution rack requirements: