Mitsubishi Electronics MR-J2S- CL Manual De Usuario
4 - 30
4. OPERATION
(b) Using the input signals for setting
Set the pulse generator multiplication 1 (TP0) and pulse generator multiplication 2 (TP1) to the
input signals in "Device setting" on the Servo Configuration Software (refer to Chapter 6).
input signals in "Device setting" on the Servo Configuration Software (refer to Chapter 6).
Pulse generator multiplication 2
(across TP1)
Pulse generator multiplication 1
(across TP0)
Multiplication ratio of servo motor
rotation to manual pulse generator
rotation
Moving distance
0
0
Parameter No.1 setting valid
0
1
1 time
1[ m]
1
0
10 times
10[ m]
1
1
100 times
100[ m]
Note. 0: OFF
1: ON
(4) Operation
Turn the manual pulse generator to rotate the servo motor. For the rotation direction of servo motor,
refer to (2) in this section.
refer to (2) in this section.