−  39  − 
 
6F8A0870
 
(3) Connecting the input signal cable 
 
Strip the sheath from the end of each conductor of a 2-core individually shielded cable as shown in Figure 
5.4. Twist those shields and cover them with a thermal contraction tube or vinyl tube not to make contact 
with the case or core wires. Then attach an M3.5 crimping terminal with insulated sleeve as shown in Figure 
5.3. Connect a crimping terminal to the A and B terminals on the terminal block and connect to each G 
terminal of the detector and converter. 
 
                     
 
       
Figure 5.3    Terminal Treatment of Flow Rate Signal Cable 
 
  Notes on signal cable shield processing work 
 
When stripping an external sheath, intermediate and insulated sheath, be careful not to scratch or cut the 
internal conductors and shield mesh. Do not disjoint the shield mesh but treat it as shown in Figure 5.9. 
       
 
Figure 5.4    Treating the Signal Cable Shield Mesh 
 
M3.5 crimping terminal 
Thermal contraction tube or vinyl tube 
A Black 
G Shield 
B White 
 25~45mm 
Shield mesh 
a.  Open the shield mesh with a pencil or the like. 
b.  Pull out the internal coated wires from the hole of the 
shielded mesh. 
c.  Pull out all internal coated wires and extend the shield mesh 
wire. 
Coated wire 
Separate