CHAPTER 7:  Alarm Configuration
 
113
7.3. 
The Circuit Breaker Open Alarm
The Circuit Breaker Alarm is intended to provide notification in the event that one 
of the Outlet Managed PDU’s circuit breakers is opened.  When a circuit breaker is 
open, the Outlet Managed PDU can provide prompt notification via Email, Syslog 
Message or SNMP Trap.
Notes:
•  The Circuit Breaker Open Alarm is not applicable to some Outlet 
Managed PDU models.
•  In order for the Outlet Managed PDU to provide alarm notification 
via Email, communication parameters must first be defined as 
described in Section 5.9.11.
•  In order for the Outlet Managed PDU to provide alarm notification 
via Syslog Message, Syslog parameters must first be defined and 
Syslog Messages must be enabled as described in Section 5.9.2 
and Section 11.
•  In order for the Outlet Managed PDU to provide alarm notification 
via SNMP Trap, SNMP parameters must first be defined, and 
SNMP Traps must be enabled as described in Section 5.9.7 and 
Section 12.
To configure the Circuit Breaker Alarm, you must access the Outlet Managed PDU 
command mode using a password that permits Administrator Level commands.  The 
Circuit Breaker Open Alarm Configuration Menu offers the following parameters:
•  Trigger Enable:  Enables/Disables the trigger for this alarm.  When 
Disabled, this alarm will be suppressed.  (Default = On.)
Note:
To cancel an alarm without correcting the condition that caused the 
alarm, simply toggle the Trigger Enable parameter Off and then back 
On again.
•  Resend Delay:  Determines how long the Outlet Managed PDU will wait to 
resend an email message generated by this alarm, when the initial attempt to 
send the notification was unsuccessful.  (Default = 60 Minutes.)
•  Notify Upon Clear:  When this item is enabled, the Outlet Managed PDU 
will send additional notification when the situation that caused the alarm has 
been corrected.  For example, when Notify Upon Clear is enabled, the Outlet 
Managed PDU can send initial notification when it detects an open circuit 
breaker, and then send a second notification when it determines that the 
circuit breaker has been closed.  (Default = On.)