Guardian Technologies 004988-4 Manual De Usuario

Descargar
Página de 48
 10 
2.5  
EMERGENCY CIRCUIT ISOLATION 
METHOD
This prevents overloading the generator by keeping 
electrical loads below the wattage/amperage capacity 
of the generator. If the generator can only power criti-
cal loads, within it’s wattage/amperage capacity, dur-
ing utility power outages, use the emergency circuit 
isolation method.
Critical electrical loads are grouped together and 
wired into a separate “Emergency Distribution Panel.” 
Load circuits powered by that panel are within the 
wattage/amperage capacity of the generator set. The 
transfer switch must meet the following require-
ments:
• It must have an ampere rating equal to the total 
amperage rating of the emergency distribution 
panel circuit.
• Have it installed between the building’s main dis-
tribution panel and the emergency distribution 
panel.
2.6  
TOTAL CIRCUIT ISOLATION 
METHOD
When a generator capable of powering all electrical 
loads in the circuit is to be installed, use the “Total 
Circuit Isolation Method.” It is possible for the gen-
erator to be overloaded when this isolation method is 
employed. The following apply to the transfer switch 
in this type of system.
• Ampere rating of the transfer switch must equal 
the ampere rating of the normal incoming utility 
service.
• The transfer switch is installed between the util-
ity service entrance and the building distribution 
panel.
2.7  GROUNDING THE GENERATOR
The National Electrical Code requires the frame and 
external electrically conductive parts of this equip-
ment to be properly connected to an approved earth 
ground and/or grounding rods. For that purpose, a 
GROUND LUG (Figure 2.2) is provided on the gen-
erator mounting base. Consult a qualified electrician 
for grounding requirements in the area. Grounding 
procedures must meet local regulations.
Figure 2.2 – Generator Grounding Lug (typical)
GROUNDING
LUG
DANGER
  Do not connect the ground wire to any pipe 
that carries a flammable or explosive substance 
– FIRE or an EXPLOSION may result.
Proper grounding helps protect personnel against 
electrical shock in the event of a ground fault condi-
tion in the generator or in connected electrical devic-
es. In addition, grounding helps dissipate static elec-
tricity that often builds up in ungrounded devices.
2.8  
GENERATOR AC NEUTRAL 
CONNECTIONS
The manufacturer uses an UNGROUNDED AC neu-
tral. Grounding is recommended only at the main 
service entrance. If the neutral wire is grounded and 
one of the phase loads becomes grounded, the exces-
sive current opens the load circuit breaker or col-
lapses the generator field. The actual result depends 
on the electrical characteristics of the particular 
installed generator.
  Failure to connect the generator neutral proper-
ly will result in unbalanced line-to-neutral volt-
ages. Resulting high voltages will cause equip-
ment damage.
2.9  
TRANSFER SWITCH SIGNAL 
CONNECTIONS
2.9.1 PRE-PACKAGED 
ATS
If the generator is to be installed with a pre-packaged 
(non-control board based) transfer switch, it is nec-
essary to connect the control wires to the generator 
and set position two of the four-position dip switch 
to OFF.
Setting switch two to OFF allows the control PCB to 
perform the ATS control functions.
‹
Section 2 — Installation
Liquid-cooled 30 kW Generators