Guardian Technologies 004988-4 Manual De Usuario
10
2.5
EMERGENCY CIRCUIT ISOLATION
METHOD
METHOD
This prevents overloading the generator by keeping
electrical loads below the wattage/amperage capacity
of the generator. If the generator can only power criti-
cal loads, within it’s wattage/amperage capacity, dur-
ing utility power outages, use the emergency circuit
isolation method.
electrical loads below the wattage/amperage capacity
of the generator. If the generator can only power criti-
cal loads, within it’s wattage/amperage capacity, dur-
ing utility power outages, use the emergency circuit
isolation method.
Critical electrical loads are grouped together and
wired into a separate “Emergency Distribution Panel.”
Load circuits powered by that panel are within the
wattage/amperage capacity of the generator set. The
transfer switch must meet the following require-
ments:
wired into a separate “Emergency Distribution Panel.”
Load circuits powered by that panel are within the
wattage/amperage capacity of the generator set. The
transfer switch must meet the following require-
ments:
• It must have an ampere rating equal to the total
amperage rating of the emergency distribution
panel circuit.
panel circuit.
• Have it installed between the building’s main dis-
tribution panel and the emergency distribution
panel.
panel.
2.6
TOTAL CIRCUIT ISOLATION
METHOD
METHOD
When a generator capable of powering all electrical
loads in the circuit is to be installed, use the “Total
Circuit Isolation Method.” It is possible for the gen-
erator to be overloaded when this isolation method is
employed. The following apply to the transfer switch
in this type of system.
loads in the circuit is to be installed, use the “Total
Circuit Isolation Method.” It is possible for the gen-
erator to be overloaded when this isolation method is
employed. The following apply to the transfer switch
in this type of system.
• Ampere rating of the transfer switch must equal
the ampere rating of the normal incoming utility
service.
service.
• The transfer switch is installed between the util-
ity service entrance and the building distribution
panel.
panel.
2.7 GROUNDING THE GENERATOR
The National Electrical Code requires the frame and
external electrically conductive parts of this equip-
ment to be properly connected to an approved earth
ground and/or grounding rods. For that purpose, a
GROUND LUG (Figure 2.2) is provided on the gen-
erator mounting base. Consult a qualified electrician
for grounding requirements in the area. Grounding
procedures must meet local regulations.
external electrically conductive parts of this equip-
ment to be properly connected to an approved earth
ground and/or grounding rods. For that purpose, a
GROUND LUG (Figure 2.2) is provided on the gen-
erator mounting base. Consult a qualified electrician
for grounding requirements in the area. Grounding
procedures must meet local regulations.
Figure 2.2 – Generator Grounding Lug (typical)
GROUNDING
LUG
DANGER
Do not connect the ground wire to any pipe
that carries a flammable or explosive substance
– FIRE or an EXPLOSION may result.
– FIRE or an EXPLOSION may result.
Proper grounding helps protect personnel against
electrical shock in the event of a ground fault condi-
tion in the generator or in connected electrical devic-
es. In addition, grounding helps dissipate static elec-
tricity that often builds up in ungrounded devices.
electrical shock in the event of a ground fault condi-
tion in the generator or in connected electrical devic-
es. In addition, grounding helps dissipate static elec-
tricity that often builds up in ungrounded devices.
2.8
GENERATOR AC NEUTRAL
CONNECTIONS
CONNECTIONS
The manufacturer uses an UNGROUNDED AC neu-
tral. Grounding is recommended only at the main
service entrance. If the neutral wire is grounded and
one of the phase loads becomes grounded, the exces-
sive current opens the load circuit breaker or col-
lapses the generator field. The actual result depends
on the electrical characteristics of the particular
installed generator.
tral. Grounding is recommended only at the main
service entrance. If the neutral wire is grounded and
one of the phase loads becomes grounded, the exces-
sive current opens the load circuit breaker or col-
lapses the generator field. The actual result depends
on the electrical characteristics of the particular
installed generator.
Failure to connect the generator neutral proper-
ly will result in unbalanced line-to-neutral volt-
ages. Resulting high voltages will cause equip-
ment damage.
ages. Resulting high voltages will cause equip-
ment damage.
2.9
TRANSFER SWITCH SIGNAL
CONNECTIONS
CONNECTIONS
2.9.1 PRE-PACKAGED
ATS
If the generator is to be installed with a pre-packaged
(non-control board based) transfer switch, it is nec-
essary to connect the control wires to the generator
and set position two of the four-position dip switch
to OFF.
(non-control board based) transfer switch, it is nec-
essary to connect the control wires to the generator
and set position two of the four-position dip switch
to OFF.
Setting switch two to OFF allows the control PCB to
perform the ATS control functions.
perform the ATS control functions.
Section 2 — Installation
Liquid-cooled 30 kW Generators