Guardian Technologies 004988-4 Manual De Usuario

Descargar
Página de 48
  
11
Control system interconnections consist of N1 and 
N2, and leads 23 and 194. Control system intercon-
nection leads must be run in a conduit that is sepa-
rate from the AC power lead. Recommended wire 
gauge sizes for this wiring depends on the length of 
the wire, as recommended below:
2.9.2 GTS-TYPE 
ATS
If the generator is to be installed with an automatic 
transfer switch, such as an engineered GTS-type 
switch, it is necessary to connect the two-wire start 
control system.
Connect the two-wire start signal from the automatic 
transfer switch to the automatic start connection, 
which is located in the middle, on the bottom, inside 
the control panel. Match wires 178 and 183 in the 
transfer switch to 178 and 183 on the terminal strip 
in the control panel. The conductors for the two-
wire start circuit must be in their own conduit. (See 
Section 3.1 for further explanation.)
2.10 BATTERY INSTALLATION
DANGER
  Standby generators installed with automatic 
transfer switches will crank and start automati-
cally when NORMAL (UTILITY) source voltage is 
removed or is below an acceptable preset level. 
To prevent such automatic start-up and possible 
injury to personnel, ensure that the 15A and 
4A fuses are removed from the control console, 
the AUTO/OFF/MANUAL switch is set to OFF, 
and the utility supply to the battery charger is 
removed before removing or connecting battery 
cables.
  Storage batteries give off explosive hydrogen 
gas. This gas can form an explosive mixture 
around the battery for several hours after charg-
ing. The slightest spark can ignite the gas and 
cause an explosion. Such an explosion can shat-
ter the battery and cause blindness or other 
injury. Any area that houses a storage battery 
must be properly ventilated. Do not allow smok-
ing, open flame, sparks or any spark producing 
tools or equipment near the battery.
‹
  Battery electrolyte fluid is an extremely caus-
tic sulfuric acid solution that can cause severe 
burns. Do not permit fluid to contact eyes, skin, 
clothing, painted surfaces, etc. Wear protective 
goggles, protective clothing and gloves when 
handling a battery. If fluid is spilled, flush the 
affected area immediately with clear water.
  Spilled electrolyte is to be washed down with 
an acid neutralizing agent. A common practice 
is to use a solution of one pound (500 grams) 
bicarbonate of soda to one gallon (4 liters) of 
water. The bicarbonate of soda solution is to be 
added until the evidence of reaction (foaming) 
has ceased. The resulting liquid is to be flushed 
with water and the area dried.
  Do not dispose of the battery in a fire. The 
battery is capable of exploding.
  Do not open or mutilate the battery. Released 
electrolyte can be toxic and harmful to the skin 
and eyes.
  The battery represents a risk of high short circuit 
current. When working on the battery, always 
remove watches, rings or other metal objects, 
and only use tools that have insulated handles.
When replacing batteries, use the same number 
and type of battery. The recommended batteries are 
Group 26, 12V negative ground 525 CCA/75 AH mini-
mum capacity, or Group 27F, 12V negative ground 
600 CCA/90 AH minimum capacity. All batteries 
must be at 100 percent state-of-charge before they 
are installed on the generator.
When using maintenance-free batteries, it is not 
necessary to check the specific gravity or electrolyte 
level. Have these procedures performed at the inter-
vals specified in Section 4, “Maintenance.” A nega-
tive ground system is used. Battery connections are 
shown on the wiring diagrams. Make sure all batter-
ies are correctly connected and terminals are tight. 
Observe battery polarity when connecting batteries to 
the generator set.
NOTE:
Damage will result if the battery connections are 
made in reverse.
2.11 PREPARATION BEFORE START-UP
The instructions in this section assume that the 
standby generator has been properly installed, ser-
viced, tested, adjusted and otherwise prepared for 
use by a competent, qualified installation contractor. 
Be sure to read the “Safety Rules” on Pages 2 and 3, 
as well as all other safety information in this manual, 
before attempting to operate this (and related) equip-
ment.
Section 2 — Installation
Liquid-cooled 30 kW Generators
 MAXIMUM 
WIRE 
LENGTH 
RECOMMENDED 
WIRE
  
SIZE
 
460 feet (140m) 
No. 18 AWG.
 
461 to 730 feet (223m) 
No. 16 AWG.
 
731 to 1,160 feet (354m) 
No. 14 AWG.
 
1,161 to 1,850 feet (565m) 
No. 12 AWG.