MANUAL — The control board will start and run 
the generator whenever the switch is in the manual 
position.
AUTO — The control board will monitor the two-
wire start circuit. When a two-wire start is issued the 
control board will immediately start and run the gen-
erator. Whe the two-wire start is removed the control 
board will immediately stop the generator.
NOTE:
If the generator is installed in conjunction with an 
engineered GTS type transfer switch, refer to the 
applicable transfer switch manual for exact oper-
ating parameters and timing sequences.
3.2  
CONTROL CONSOLE
COMPONENTS
The components of a home standby generator control 
console (Figure 3.1) are as follows:
3.2.1 AUTO/OFF/MANUAL 
SWITCH
Use this three-position switch as follows:
•  Set the switch to AUTO for fully automatic opera-
tion. See “Automatic Operation” (Section 3.6).
•  Set switch to MANUAL position to crank and start 
the generator engine.
•  Set switch to OFF position to shut down an operat-
ing engine. With OFF selected, operation will not 
be possible.
Figure 3.1 - Home Standby Generator Panel
E
US
U
F
F
E
US
U
F
(SEE OWNER'S MANUAL FOR COMPLETE LED DETAILS)
5 FLASHING RED LED'S = EXERCISER NOT SET
FLASHING GREEN LED = NO UTILITY SENSE
TO SET EXERCISER TIME
1) PLACE AUTO/OFF/MANUAL SWITCH TO AUTO POSITION.
(IN AUTO MODE ONLY) SOLID GREEN LED = SYSTEM READY, UTILITY POWER ON
OFF
EXERCISE
TIME
ON
SET
LED INDICATORS:
RED LED'S = INDIVIDUAL FAULT
MANUAL
OFF
AUTO
0E7194
OVER CRANK
AUTO/OFF/MANUAL
SWITCH
15A FUSE
MAIN
POWER
4A FUSE
BATTERY
CHARGER
SET
EXECISER
TIME
SWITCH
RED LED
GREEN LED
‹
DANGER
  With switch set to AUTO, engine can crank and 
start suddenly without warning. Such automatic 
start up normally occurs when utility source 
voltage drops below a pre-set level. To prevent 
possible injury that might be caused by such 
sudden starts, set AUTO/OFF/MANUAL switch 
to OFF before working on or around the unit. 
Then, place a “DO NOT OPERATE” tag on control 
console.
3.2.2  FAULT INDICATOR LED
This LED goes ON when one or more of the following 
engine faults occurs and when engine shuts down.
• Low Oil Pressure
• Overcrank
• Low Battery
• Overspeed/RPM Sensor Loss
•  High Coolant Temperature/Low Coolant Level
See Section 1.7 for further explanation of engine pro-
tection functions.
3.2.3  15 AMP FUSE
Fuse protects the control console’s DC control circuit 
against electrical overload. If the fuse has melted 
open because of an overload, engine cranking and 
startup cannot occur. If the fuse needs to be replaced, 
use only an identical 15-amp replacement fuse. (Type 
AGC)
3.2.4  4.0 AMP INLINE FUSE
This fuse protects the battery charger against electri-
cal overload. If the fuse needs to be replaced, use only 
an identical 4 amp replacement fuse (type AG).
NOTE:
This fuse will not remove the + battery input 
power from the PCB when it opens. This means 
the exercise timer will not be reset.
3.2.5  SET EXERCISE TIME SWITCH
This switch allows programming the generator to 
start and exercise automatically. “See Weekly Exercise 
Cycle.”
3.2.6  SYSTEM READY LED
The System Ready LED (green) has two main pro-
poses. First, the LED will be ON when the AUTO/
OFF/MANUAL switch is in the AUTO position, utility 
is present, and there are no system alarms. This ON 
state indicates the system is fully ready for automatic 
operation.
‹
‹
‹
‹
‹
Section 3 - Operation
Liquid-cooled 30 kW Generators