1.1 GENERATOR
This equipment is a liquid-cooled, engine-driven 
generator set. The generator is designed to supply 
electrical power that operates critical electrical loads 
during utility power failure. The unit has been facto-
ry-installed in a weather resistant, all metal enclosure 
and is intended for outdoor installation only. Use 
this generator as a source of electrical power for the 
operation of 120 and/or 240VAC, single-phase loads.
   If this generator is used to power electrical load 
circuits normally powered by a UTILITY power 
source, it is required by code to install a trans-
fer switch. The transfer switch must effectively 
isolate the electric system from the utility distri-
bution system when the generator is operating 
(NEC 701). Failure to isolate an electrical system 
by such means results in damage to the genera-
tor and may also result in injury or even death 
to utility power workers due to backfeed of 
electrical energy.
1.2 TRANSFER 
SWITCH
This generator system may include a matched auto-
matic transfer switch which is intended to be used 
in conjunction with the generator. It is supplied in 
a NEMA 3R enclosure. The NEMA 3R enclosure is 
weather proof and can be used indoors or outdoors. 
Follow these rules:
• Install the transfer switch on a firm, sturdy sup-
porting structure.
• To prevent switch distortion, level the switch if 
necessary. This can be done by placing washers 
between the switch enclosure and the mounting 
surface.
•  Never install the switch where water or any corro-
sive substance might drip onto the enclosure.
• Protect the switch at all times against excessive 
moisture, dust, dirt, lint, construction grit and cor-
rosive vapors.
If a transfer switch is not included, one may be pur-
chased separately from an Authorized Dealer.
1.3 AUTOMATIC 
SYSTEM OPERATION
When this generator, along with a transfer switch, has 
been installed and interconnected, a circuit board 
in the generator panel constantly monitors UTILITY 
power source voltage. Should that voltage drop below 
a preset value, and remain at such a low state for 
a preset amount of time, the generator cranks and 
starts. After the generator starts, the transfer switch 
transfers load circuits so the generator can power 
them.
When UTILITY source voltage has been restored, the 
switch re-transfers back to the UTILITY source volt-
age and the generator then shuts down.
Please reference the transfer switch manual for spe-
cific information.
1.4  
GENERATOR AC CONNECTION 
SYSTEMS
The generator was shipped from the factory with its 
stator AC output leads connected in a single-phase, 
three-wire generator AC connection system (Figure 
1.1). The stator assembly in this system consists of 
a pair of stationary windings, with two leads brought 
out of each winding. Each single winding can sup-
ply 120VAC, 60 Hertz. When the two windings are 
connected in series, a 240VAC, 60 Hertz AC output 
results. Typically the two HOT leads in the circuit 
are wires 11 and 44. The NEUTRAL leads are the 
junction of Wires 22 and 33. The NEUTRAL is not 
grounded.
Figure 1.1 - Generator AC Connection System
1.5  MAIN CIRCUIT BREAKER
The generator’s main circuit breaker is included with 
the unit as shipped from the factory. The breaker for 
each unit is described in Figure 1.2.
Section 1 - General Information
Liquid-cooled 30 kW Generators
 Model 
Rating 
Phase 
Actual 
Current 
C/B 
Rating* 
Circuit 
Breaker
 004988-4 
27,000 
NG 
112.5 
150 
150A 
QN2
 
 
30,000 LP 
125.0 
150 
150A QN2
* Amp Rating of C/B structured under model.
Figure 1.2 - Main Circuit Breaker