Siemens CGGV Manual De Usuario

Descargar
Página de 38
- 9 - 
Installation 
 
Tests Before Operation 
Insulation Resistance 
Check insulation resistance prior to connecting motor 
to power supply.  A hand cranked or solid state 
electronic insulation resistance tester, at least 500 volts 
d.c., but not over rated voltage, is usually used (see 
Maintenance). 
 
See IEEE Recommended Practice for Testing 
Insulation Resistance Rotating Machinery IEEE Std 43. 
 
Dielectric (Hi-Pot) Tests 
All motors receive a factory dielectric test in 
accordance with ANSI and IEEE Standards. 
 
 
 
DANGER
 
Dielectric testing may result in 
personal injury or death. 
Operate dielectric test equipment only 
with qualified personnel, in accordance 
with manufacturer’s instructions. 
 
If a dielectric test is made on an old or repaired 
winding, to evaluate service reliability, the test voltage 
applied may vary from the rated terminal voltage to 
some higher value.  The factory should be consulted 
when establishing the tes
t voltage and procedure for testing 
old or repaired equipment. 
 
CAUTION
 
Excessive dielectric testing may cause damage to 
insulation. 
Test only in accordance with IEEE Std. 43. 
 
Winding Resistance (Temperature) 
The change in resistance of a winding provides an 
accurate measure of the average temperature of a 
winding, and is generally used to determine the 
temperature of the stator windings.  The 
measurements must be made carefully with 
instruments known to be accurate, and preferably with 
the same instruments for both hot and cold 
measurements. 
 
NOTE
 
If normal vibration or noise will be objectionable (as in 
Instruments that operate on the principle of the Kelvin 
Bridge are preferred.  (See "Temperature Measuring 
Devices" - IEEE Publication No. 119.) 
 
The cold resistance, or the resistance at normal room 
temperature, must be measured after the machine has 
been idle for some time, usually before starting, or cold 
resistance value may be obtained from the factory.  
The cold temperature of the coils should be measured 
because coil temperature may not be the same as the 
surrounding air. 
 
The average temperature of the winding is obtained by 
taking resistance measurements, at the motor load 
terminals and using the following equation: 
 
5
.
234
)
5
.
234
(
+
=
t
r
R
T
 
 
Where    T = hot temperature in degrees C 
 
R = hot resistance 
 
r  = cold resistance at temperature t 
 
t = cold temperature of winding in deg C (amb) 
 
As an example, assume the cold resistance of 0.50 
ohms at 25
°C, and the hot resistance (taken 
immediately after motor is de-energized, and has 
stopped rotating) is 0.61 ohms, then: 
 
5
.
234
)
25
5
.
234
(
50
.
0
61
.
0
+
=
T
 
 
82
=
T
 
 
The temperature measured by imbedded detectors or 
by the change in resistance is generally higher than 
thermometer measurements and is closer to the true 
hottest spot temperature in the machine.  For this 
reason, the Standards permit higher observable 
temperatures when measurements are taken in this 
manner.