 18
Potable Water and Space Heating
1. All piping materials and components connected to
the water heater for the space heating application
shall be suitable for use with potable water.
2. Toxic chemicals, such as used for boiler treatment,
shall not be introduced into the potable water used
for space heating.
3. If the heater will be used to supply potable water,
it shall not be connected to any heating system or
components  previously  used  with  a  non-potable
water heating appliance.
CAUTION: When  this  heater  is  used  for  both
potable  water  and  space  heating,  observe  the
following to ensure proper operation.
TANK SENSOR
Fig. 13: Single Domestic Hot Water Heater and Storage
Tank
Table I:  Domestic Water Heater Flow Rate Requirements
4. When the system requires water for space heating
at temperatures higher than 140°F, a means such
as a mixing valve shall be installed to temper the
water in order to reduce scald hazard potential.
Pool Heating
The Hi Delta pool heater is equipped with an external
pump  and  bypass  arrangement  as  standard  equip-
ment.  This  arrangement  blends  outlet  water  with  the
inlet  water  to  increase  the  inlet  water  temperature,
thereby reducing the likelihood of condensation form-
ing on the heat exchanger. The pump also serves to
circulate water through the heater from the main sys-
tem piping.
To complete the installation of the pool heater, the pool
thermostat needs to be installed in the main return wa-
ter  line,  upstream  of  the  heater. This  will  ensure  that
the  heater  will  be  energized  at  the  right  time.  If  the
main water line is too far away from the heater and the
capillary bulb will not reach it, locate the pool thermo-
stat adjacent to the main line and run wires back to the
heater.
CAUTION: Power  to  the  heater  should  be
interlocked with the main system pump to make sure
the  heater  does  not  fire  without  the  main  system
pump  in  operation.  Improper  flow  control  can
damage  the  heater.  Uncontrolled  flow  (too  high)  or
restricted  flow  (too  low)  can  seriously  damage  the
heater. Follow these instructions to make sure your
heater is properly installed.
∆T = Temperature rise, °F
∆P = Pressure drop through heat exchanger, ft
SHL = System head loss, ft.  Includes 50 eq ft of tubing each way (total 100 eq ft).
gpm = Gallons per minute, flow rate
MTS = Minimum tubing size
*Must utilize optional cupro-nickel tubes. If over 25 grains per gallon, a water softener/treatment system must be utilized.
Caution: For scale free operation with "Hard Water" (16-25 grains per gallon of total hardness), the operating control must NOT be
set higher than 130 °F. For higher than 130 °  F operation, a water softener/treatment system must be utilized.
Model
No.
Soft (0-4 grains per gallon)
Medium (5-15 grains per gallon) Hard* (16-25 grains per gallon)
T
gpm
P
MTS SHL
T
gpm
P
MTS
SHL
T
gpm
P
MTS SHL
302B
13
40
2.0
2
5.1
10
52
3.3
2
8.3
7
74
6.6
2
16.3
402B
17
40
2.0
2
5.1
13
52
3.4
2
8.4
9
74
6.8
2
16.4
502B
21
40
2.1
2
5.2
16
52
3.5
2
8.6
12
73
6.9
2
16.3
652B
28
40
2.2
2
5.3
20
55
4.1
2
9.7
15
72
7.0
2
16.2
752B
30
42
2.6
2
6.0
17
73
7.5
2
16.9
14
90
11.3
2
25.1
902B
30
51
3.9
2
8.7
21
73
7.8
2
17.2
17
90
11.7
2
25.5