A  thermostatically  controlled  mixing  valve  is  used  to
mix the outlet water with the pool water.  This mixed
water is supplied as the inlet water to the pool heater.
The  proper  configuration  is  shown  in  Fig.  15.    The
active element of the valve adjusts the mixing ratio to
maintain the inlet water above 105°F.  
MIXING VALVE
Fig. 14: Single Pool Heater Application
Automatic Chlorinators and Chemical
Feeders
All  chemicals  must  be  introduced  and  completely  di-
luted into the pool or spa water before being circulated
through  the  heater.  Do  not  place  chlorine  tablets  or
bromine sticks in the skimmer. High chemical concen-
trations will result when the pump is not running (e.g.
overnight).
Chlorinators must feed downstream of the heater and
have  an  anti-siphoning  device  to  prevent  chemical
back-up into the heater when the pump is shut off.
Winterizing Your Heater
Heaters  installed  outdoors  in  freezing  climate  areas
should  be  shut  down  for  the  winter.  To  shut  down
heater, turn off manual main gas valve and main gas
shut-off. Close isolation valves and remove water pip-
ing  from  the  in/out  header  on  the  heater.  Drain  the
heater and any piping of all water that may experience
below-freezing temperatures.
Pool/Spa Water Chemistry
Water Hardness
Water hardness is mainly due to the presence of cal-
cium and magnesium salts dissolved in the water. The
concentration of these salts is expressed in mg/l, ppm
or grains per gallon, as a measure of relative hardness
of  water.  Grains  per  gallon  is  the  common  reference
measurement used in the U.S. water heater industry.
Hardness expressed as mg/L or ppm may be divided
by 17.1 to convert to grains per gallon. Water may be
classified as very soft, slightly hard, moderately hard
or  hard  based  on  its  hardness  number.  The  salts  in
water will precipitate out when the water is heated and
will cause accelerated lime and scale accumulation on
a heat transfer surface.
Fig. 15: Mixing Valve Configuration
CAUTION: Combustion  air  must  not  be
contaminated  by  corrosive  chemical  fumes  which
can damage the heater and void the warranty.
NOTE: High  chemical  concentrates  from  feeders
and chlorinators that are out of adjustment will cause
very  rapid  corrosion  of  the  heat  exchanger  in  the
heater.  Such  damage  is  not  covered  under  the
warranty.
NOT      E: Chemical  imbalance  can  cause  severe
damage to your heater and associated equipment.