at  test  pressures  equal  to  or  less  than  1/2  psi  (3.45
kPa). Relieve test pressure in the gas supply line prior
to  reconnecting  the  heater  and  its  manual  shut-off
valve to the gas supply line. FAILURE TO FOLLOW
THIS  PROCEDURE  MAY  DAMAGE  THE  GAS
VALVES
.  Over  pressurized  gas  valves  are  not  cov-
ered by warranty. The heater and its gas connections
shall  be  leak-tested  before  placing  the  appliance  in
operation. Use soapy water for leak test. DO NOT use
an open flame.
Reversing Gas Supply Connection
Reversing the standard fuel connection from the left-
hand to the right-hand side is a simple field operation.
1. Disconnect all electrical power from the heater (if
applicable).
2. Disconnect the main gas pipe from the heater (if
applicable).
3. Remove  the  left  and  right  front  panels  from  the
heater.
4. Locate the main gas line that traverses across the
heater above the manifold risers.
5. Remove  the  pipe  cap  from  the  right-hand  end  of
the main gas line.
21
Gas Supply
Gas  piping  must  have  a  sediment  trap  ahead  of  the
heater  gas  controls,  and  a  manual  shut-off  valve  lo-
cated  outside  the  heater  jacket.  It  is  recommended
that a union be installed in the gas supply piping adja-
cent  to  the  heater  for  servicing.  A  pounds-to-inches
regulator  must  be  installed  to  reduce  the  gas  supply
pressure to  a maximum of 10.5 in. WC for natural gas
and 13.0 in. WC for propane gas. The regulator should
be  placed  a  minimum  distance  of  10  times  the  pipe
diameter up-stream of the heater gas controls. Refer
to Table K for maximum pipe lengths.
Gas Supply Connection
The heater must be isolated from the gas supply pip-
ing system by closing the manual shut-off valve during
any pressure testing of the gas supply piping system
CAUTION: The heater must be disconnected from
the gas supply during any pressure testing of the gas
supply system at test pressures in excess of 1/2 psi
(3.45 kPa). 
Fig. 16: Gas Supply Connection
CAUTION: Do not use Teflon tape on gas line pipe
thread. A pipe compound rated for use with natural
and  propane  gases  is  recommended.  Apply
sparingly  only  on  male  pipe  ends,  leaving  the  two
end threads bare.
CAUTION: Support  gas  supply  piping  with
hangers, not by the heater or its accessories. Make
sure  the  gas  piping  is  protected  from  physical
damage and freezing, where required.
3/4"
1”
1-1/4”
1-1/2”
2”
2-1/2”
Model
No.
N
P
N
P
N
P
N
P
N
P
N
P
302B
15
25
35
85
150
380
360
--
--
--
--
--
402B
--
15
25
60
100
260
250
--
--
--
--
--
502B
--
--
--
--
65
150
130
360
500
--
--
--
652B
--
--
--
--
45
100
95
250
340
--
--
--
752B
--
--
--
--
35
80
75
180
260
600
--
--
902B
--
--
--
--
20
45
45
110
150
360
400
--
Table K:  Maximum Equivalent Pipe Length
DANGER: Make sure the gas on which the heater
will  operate  is  the  same  type  as  specified  on  the
heater’s rating plate.
Natural gas – 1,000 BTU per ft
3
, .60 specific gravity at 0.5 in. WC pressure drop
Propane gas – 2,500 BTU per ft
3
, 1.53 specific gravity at 0.6 in. WC pressure drop