Cisco ASR 9001 and Cisco ASR 9001-S Routers Hardware Installation Guide
OL-26701-02
Chapter 5 Replacing Cisco ASR 9001 Router Components
Removing a Chassis from the Equipment Rack
Figure 5-2
Removing or Installing an AC or DC Power Module
Installing an AC or DC Power Module
To install an AC or DC power module (see
):
Step 1
Slide the power module into the bay until it mates with its backplane connector.
Step 2
Make sure that keying lever locks with the chassis.
Step 3
Verify that the OK (green) power indicator on the front of the power module comes ON. If the indicator
does not light up, see the
does not light up, see the
Removing a Chassis from the Equipment Rack
Use this procedure to remove the chassis and its components from the equipment rack:
Warning
You must use two people to remove the chassis from the equipment rack safely. An empty chassis can
weigh up to approximately
weigh up to approximately
24.69 pounds (11.2 kg)
.
Step 1
Power off the router (see the
).
Step 2
Power off the circuit breakers to the power supplies.