Publication 1734-UM011C-EN-P - January 2006
4-24        Configure the Adapter for Direct Connection in RSLogix 5000 Software
Recover From an 
Overloaded Adapter
Each POINT I/O connection established with the 1734-AENT adapter  
consumes a portion of the microprocessor’s bandwidth. The amount 
of bandwidth used by a connection depends on a number of 
variables, including the requested packet interval (RPI), the number of 
POINT I/O modules involved in the connection, and the rate of 
change of the I/O. 
The 1734-AENT adapter continuously monitors this bandwidth and 
rejects requests for new connections when there is insufficient 
bandwidth available to support the new connection.
The condition where the 1734-AENT adapter cannot support the 
connection due to a limit of the microprocessor’s bandwidth is shown 
in the following dialog. 
If you encounter this condition, the only action you can take is to alter 
the existing connections to reduce the amount of microprocessor 
bandwidth consumed. The most likely fixes for this condition include 
the following.
• Increase the RPI.
• Decrease the number of connections.