Publication 1734-UM011C-EN-P - January 2006
5-2        Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
Set Up the Hardware
In this example, a ControlLogix chassis contains the Logix 5555 
controller in slot 1 and a 1756-ENBT bridge module in slot 3. We 
mounted the 1734-AENT adapter on a DIN rail in slot 0, with a 
1734-OW2/C relay output module in slot 1, a 1734-OV4E/C sink 
output module in slot 2, and a power supply (not shown).
To work along with this example, set up your system as shown in the 
figure.
• Note that in the example application, the Logix5555 controller 
and 1756-ENBT module (firmware revision 2.3 or later) we 
assume are in the slots shown in the figure. 
• Verify the IP addresses for your programming terminal, 
1756-ENBT module, and 1734-AENT adapter.
• Verify the position (slot) of the I/O modules on the DIN rail.
• Verify that you properly connected all wiring and cabling. 
• Be sure you configured your communication driver (such as 
AB_ETH-1 or AB-ETHIP-1) in RSLinx software as described in 
the Configure the RSLinx Ethernet Communication Driver 
appendix of this manual.
Local 
Chassis
POINT I/O
Logix5555
Controller (slot 1)
1756-ENBT 
10.88.70.4 (slot 3)
Data
Switch
10.88.70.26
Programming 
Terminal
Slot    0   1   2   3
1734-AENT 
10.88.70.2
Slot  0  1  2   3  4 