Toshiba XLTR-200 Manual De Usuario

Descargar
Página de 99
 
  
63
13.7  Toshiba 3-Series ASD Protocol 
• 
The gateway can act as an RS232 master for Toshiba 3-series ASDs (G3, 
H3, E3 etc.)  Use of the ICC “Toshiba 3-Series ASD Interface Cable” (ICC 
part #10603) or an equivalent cable is required to connect the gateway’s 
RS232 port to the drive’s on-board RS232 port. 
 
• 
The following ASD parameters (in GROUP:COMMUNICATION SETTING 
PARAMETERS) must be set as indicated: 
 
RS232 BAUD RATE.........................2 (9600 baud) 
 
NUMBER OF DATA BITS ................1 (8 bits) 
 
PARITY SETTING...........................0 (even parity) 
Remember that the drive must be reset whenever communication-related 
parameters are changed in order to activate the change. 
 
• 
All parameter writes use the drive’s RAM / EEPROM data write (“W”) 
command.  For all writes that target the drive’s EEPROM, be sure to follow 
Toshiba’s guidelines regarding the number of times a specific parameter 
can be written without risk of EEPROM damage. 
 
• 
Point parameter number entry radix is hexadecimal (e.g. 10 = 0x0010 or 
16
10
). 
 
• 
The available ASD parameters are as indicated in the tables starting in 
section 13.7.1.  For further details on how to interpret these tables, please 
refer to the Toshiba G3 RS232C Communications Manual (Toshiba part 
number 42709) or the Toshiba INV3-MODBUS-RTU Communications 
Manual
 (ICC part number 10028).