13.7.1  Command Parameters 
Parameter 
Bit Function Bank 
Mask 
Adjustment Range 
Multiplier 
0001 word 
Frequency 
command  0 FFFF 
0.00 
∼ 400.00Hz 
Actual frequency will be limited by 
LL, UL and Fmax. 
0.01 
0002 0 
RUN 
command 
 
0: Stop 
1: Run 
 
 1 
Reserved 
 
 
 
 
 2 
Forward 
• reverse run 
selection 
  
0: 
reverse 
1: forward 
 
 
Acc/dec #1 / #2 
selection 
 
 
0: Acc / dec #1 
1: Acc / dec #2 
 
 4 
Reserved 
 
 
 
 
 5 
Reserved 
 
 
 
 
 6 
Reserved 
 
 
 
 
 
Jog mode selection 
 
 
0: Normal (acc/dec mode) 
1: Jog mode 
 
 
Feedback control 
 
 
0: Feedback valid  
1: Feedback invalid 
 
 9 
Compulsory 
DC 
injection braking mode 
 
 
0:  No compulsory DC injection 
braking 
1:  Compulsory DC injection 
below DC INJECTION 
START FREQUENCY 
 
 A 
Fundamental 
parameter switching 
 
 
0: V/F #1 
1: V/F #2 
 
 
Gate block command 
(coast stop command) 
  
0: 
Normal 
1: Gate block 
 
 C 
Emergency 
off 
command 
 
 
0: Does nothing 
1: Emergency off 
 
 D 
Reset 
command 
(trip clear) 
 
 
0: Does nothing 
1: Reset 
 
 E 
Reserved 
 
 
 
 
 F 
Reserved 
 
 
 
 
0003 
word 
RS232 command / 
frequency selection 
0 0003 
0000: 
FREQUENCY MODE 
SELECTION, COMMAND 
MODE SELECTION 
settings 
0001:  RS232C commands valid 
0002:  RS232C frequency valid 
0003:  RS232C commands and 
frequency valid 
 
0004 
word 
Preset speed run 
command 
0 000F 
0000: 
Output 
frequency 
selected by FREQUENCY 
MODE SELECTION 
0001 
∼ 000F: speeds 1 ∼ 15 
