Toshiba XLTR-200 Manual De Usuario

Descargar
Página de 99
 
  
66
Parameter 
Bit Function 
Bank 
Mask 
Adjustment Range 
Multiplier 
0012 high 
byte 
2nd  past trip 
7F00 
 
 
 low 
byte 
1st past trip (oldest) 
 
007F 
 
 
0013 word 
Pre-compensation 
output 
frequency 
0 FFFF 
0000 
∼ 9C40 
(0.00 
∼ 400.00 Hz) 
0.01 
0014 word 
Post-compensation 
output 
frequency 
0 FFFF 
0000 
∼ 9C40 
(0.00 
∼ 400.00 Hz) 
0.01 
0015 
word 
Torque current monitor 
FFFF 
(Note 2) 
0.01 
0016 low 
byte 
Excitation current monitor 
00FF 
00 
∼ FF (0 ~ 255%) 
 high 
byte 
Reserved 
 
 
 
 
0017 
word 
PID feedback value 
FFFF 
(Note 2) 
0.02 
0018 
word 
Motor overload ratio 
FFFF 
0 ~ 65535 
100/65535 
0019 
word 
Inverter overload ratio 
FFFF 
0 ~ 65535 
100/65535 
001A 
word 
DBR overload ratio 
FFFF 
0 ~ 65535 
100/65535 
001B 
word 
Input power (%) 
FFFF 
0 ~ 6553.5 
0.1 
001C 
word 
Input power (kW) 
FFFF 
(Note 3) 
 
001D 
word 
Output power (%) 
FFFF 
(Note 2) 
0.1 
001E 
word 
Output power (kW) 
FFFF 
(Note 2, Note 3) 
 
001F 
word 
RR input 
FFFF 
0 ~ 65535 
100/65535 
0020 
 
Reserved 
 
 
 
 
0021 
 
Reserved 
 
 
 
 
0022 
 
Reserved 
 
 
 
 
0023 low 
byte 
Inverter typeform monitor 
00FF 
Refer to Table 8 (page 
68) 
 
 
Input / output power units 
0100 
0: 0.01kW 
1: 0.1kW 
 
 
9,A 
Command mode status 
0600 
00: terminal 
01: panel 
10: option 
11: RS232C 
 
 
B,C 
Frequency mode selection 
status 
0 1800 
00: 
terminal 
01: panel 
10: option 
11: RS232C 
 
 D,E,F 
Reserved 
 
 
 
 
0024 
 
Reserved 
 
 
 
 
0025 
word 
Output current (amps) 
 
FFFF 
0.0 ~ 6553.5 A 
0.1 
 
(Note 1) .... These monitor voltage units are not affected by the setting of  VOLTAGE UNITS SELECTION in 
GROUP:UTILITY PARAMETERS; they are always in units of %. 
(Note 2) .... These parameters use signed data (data values larger than 7FFF
H
 are negative).  If the parameter data is 
8000
H
 or larger, the actual value can be obtained by: actual value = - [FFFF
H
 - (parameter data) + 1]
(Note 3) .... If the input / output power units data is 0, the monitored data is in 0.01kW units, and the multiplier is 0.01.  
If the input / output power units data is 1, the monitored data is in 0.1kW units, and the multiplier is 0.1.  
These values are automatically set according to the inverter’s capacity.