Toshiba XLTR-200 Manual De Usuario

Descargar
Página de 99
 
  
74
Table 10:  Output Terminal Selections (RCH, LOW, FL, OUT relay contacts) 
Setting 
Value 
Data 
(Hex) 
Function 
Setting 
Value 
Data 
(Hex) 
Function 
0000 
Lower limit frequency 
32 
C5B7 
Executing emergency off 
0100 
/Lower limit frequency 
33 
CDB7 
/Executing emergency off 
0200 
Upper limit frequency 
34 
B5BB 
Executing retry 
0300 
/Upper limit frequency 
35 
BDBB 
/Executing retry 
0400 
Low speed signal 
36 
D5CF 
Pattern run switching output 
0500 
/Low speed signal 
37 
DDCF 
/Pattern run switching output 
0600 
Accel/decel complete 
38 
D5D8 
PID deviation limit 
0700 
/Accel/decel complete 
39 
DDD8 
/PID deviation limit 
0800 
Selected speed reach signal 
40 
C5BB 
Run/stop 
0900 
/Selected speed reach signal 
41 
CDBB 
/Run/stop 
10 
0A00 
Fault 
42 
1400 
Severe fault (armature short, load-
end short, open phase, output 
error, earth fault) 
11 
0B00 
/Fault 
43 
1500 
/Severe fault (armature short, load-
end short, open phase, output 
error, earth fault) 
12 
0C00 
Fault other than earth fault or 
load-end overcurrent 
44 
1600 
Non-severe fault (overload, 
overcurrent, overvoltage) 
13 
0D00 
/Fault other than earth fault or 
load-end overcurrent 
45 
1700 
/Non-severe fault (overload, 
overcurrent, overvoltage) 
14 
95B5 
Overcurrent pre-alarm 
46 
E5D8 
Commercial power / inverter 
switching output #1 
15 
9DB5 
/Overcurrent pre-alarm 
47 
EDD8 
/Commercial power / inverter 
switching output #1 
16 
85C5 
Inverter overload pre-alarm 
48 
F5D8 
Commercial power / inverter 
switching output #2 
17 
8DC5 
/Inverter overload pre-alarm 
49 
FDD8 
/Commercial power / inverter 
switching output #2 
18 
95C5 
Motor overload pre-alarm 
50 
85C0 
Fan ON/OFF 
19 
9DC5 
/Motor overload pre-alarm 
51 
8DC0 
/Fan ON/OFF 
20 
D5C5 
Overheat pre-alarm 
52 
F5B6 
Executing JOG 
21 
DDC5 
/Overheat pre-alarm 
53 
FDB6 
/Executing JOG 
22 
A5B4 
Overvoltage pre-alarm 
54 
1800 
Local/remote operation 
23 
ADB4 
/Overvoltage pre-alarm 
55 
1900 
/Local/remote operation 
24 
E5B4 
Undervoltage alarm 
56 
A5D1 
Cumulative timer alarm 
25 
EDB4 
/Undervoltage alarm 
57 
ADD1 
/Cumulative timer alarm 
26 
85B5 
Undercurrent alarm 
58 
1A00 
Communication error alarm 
27 
8DB5 
/Undercurrent alarm 
59 
1B00 
/Communication error alarm 
28 85D1 
Overtorque 
alarm 
60 A5B6 
F/R 
29 8DD1 
/Overtorque 
alarm 
61 ADB6 
/F/R 
30 
E5BB 
Braking resistor OL pre-alarm 
62 
1E00 
Run preparation complete 
31 
EDBB 
/Braking resistor OL pre-alarm 
63 
1F00 
/Run preparation complete