13.7.7  Special Control Parameters 
Parameter 
Function / Title 
Bank 
Mask 
Adjustment Range 
Multiplier 
0069 
START-UP FREQUENCY 
0 / 1 
FFFF 
0000 
∼ 03E8 (0.00 ∼ 10.00) 
0.01 
006A 
∼ 
006F 
Reserved 
 
 
 
 
0070 
END FREQUENCY 
0 / 1 
FFFF 
0000 
∼ 0BB8 (0.00 ∼ 30.00) 
0.01 
0071 
RUN FREQUENCY 
0 / 1 
FFFF 
0000 
∼ Fmax 
0.01 
0072 
RUN FREQUENCY 
HYSTERESIS 
0 / 1 
FFFF 
0000 
∼ 0BB8 (0.00 ∼ 30.00) 
0.01 
0073 
ENABLE JUMP 
FREQUENCIES 
0 / 1 
0080 
0000: Function OFF 
(0) 
0080: Function ON 
(1) 
 
0074 
JUMP FREQUENCY #1 
0 / 1 
FFFF 
0000 
∼ Fmax 
0.01 
0075 
JUMP FREQUENCY #1 
BANDWIDTH 
0 / 1 
FFFF 
0000 
∼ 0BB8 (0.00 ∼ 30.00) 
0.01 
0076 
JUMP FREQUENCY #2 
0 / 1 
FFFF 
0000 
∼ Fmax 
0.01 
0077 
JUMP FREQUENCY #2 
BANDWIDTH 
0 / 1 
FFFF 
0000 
∼ 0BB8 (0.00 ∼ 30.00) 
0.01 
0078 
JUMP FREQUENCY #3 
0 / 1 
FFFF 
0000 
∼ Fmax 
0.01 
0079 
JUMP FREQUENCY #3 
BANDWIDTH 
0 / 1 
FFFF 
0000 
∼ 0BB8 (0.00 ∼ 30.00) 
0.01 
007A 
∼ 
007F 
Reserved 
 
 
 
 
0080 
PWM CARRIER FREQUENCY 
(Note 1) 
0 / 1 
00FF 
0005 
∼ 0064 (0.5 ∼ 10.0) 
0.1 
 