Toshiba PROSEC T3H Manual De Usuario

Descargar
Página de 73
 
User’s Manual   
11
 
1. T3H Overview 
 
 
 
1.2   Differences between T3H and T3 
 
The table below summarizes the differences between the T3H and T3. All other 
functions supported by the T3 can also be supported by the T3H as same. 
 
Item T3H 
T3 
Program memory capacity 
32 k steps (PU325H) 
64 k steps (PU326H) 
32 k steps 
(PU315 and PU325) 
Built-in EEPROM 
Yes 
(PU325H and PU326H) 
No (PU315) 
Yes (PU325) 
Programming instructions 
All T3’s instructions plus 
FUN042  D
FUN156  PID3 
FUN232  FPID3 
FUN239  SEND 
FUN240  RECV 
 
Execution speed (
µ
s) 
0.09 / contact 
0.18 / coil 
0.9 / addition 
0.15 / contact 
0.3 / coil 
1.5 / addition 
Max. number of I/O modules 
supported in local 
76 modules  
(when IF321 is used) 
43 modules 
System 
operation 
Timer interrupt interval 
setting 
1 to 1000 ms, 1 ms units 
2 to 1000 ms, 1 ms units 
 
Auto-RUN / standby 
selection 
Software setting  
(system information) 
Hardware switch 
(RAM/ROM switch) 
User data  External I/O  
(X/XW, Y/YW) 
8192 points / 512 words 
4096 points / 256 words 
 Auxiliary 
register 
(R/RW) 
16000 points /  
1000 words 
8192 points / 512 words 
 Special 
register 
(S/SW) 
4096 points / 256 words 
Same as left 
 
Timer (T./T) 
1000 points 
(proportion of 0.1s and 
0.01s timer is user 
definable) 
512 points 
(T000 - T063: 0.1s) 
(T064 - T511: 0.01s) 
 
Counter (C./C) 
512 points 
Same as left 
 
Data register (D) 
8192 words 
Same as left 
 
Link register (Z/W) 
(for TOSLINE-S20) 
16000 points /  
2048 words 
(bit access available for 
leading 1000 words) 
8192 points /  
1024 words 
(bit access available for 
leading 512 words) 
 
Link register (L/LW) 
(for TOSLINE-F10) 
4096 points / 256 words 
Same as left 
 
File register (F) 
32768 words 
8192 words 
 
Index register  
(I, J, K) 
3 words 
Same as left 
Programming tool 
T-PDS 
T-PDS and HP911 
Networking Ethernet, 
 
TOSLINE-S20, 
TOSLINE-F10, 
RS-485 computer link 
TOSLINE-S20, 
TOSLINE-F10, 
RS-485 computer link