User’s Manual   
29
 
2. Expanded Functions 
 
 
 
2.1.3 
Saving the sampling trace condition 
 
The sampling trace function is available on the T3H as well as the T3. In addition to 
all the sampling trace functions on the T3, the T3H can save the sampling trace 
condition into the IC memory card. By using this function, the sampling trace data 
which is collected and saved in the IC memory card on one T3H can be displayed 
using other T3H via the IC memory card. 
 
This function is used as follows. 
 
T3H which performs sampling (data collection): 
• 
Install the IC memory card in the T3H CPU module. 
• 
Set MMR for the PU slot in the I/O allocation in order to use an IC memory card for 
sampling data storage. 
• 
Set the special device S0620 to ON.  
• 
Edit the sampling trace condition. The edited condition is also saved into the IC 
memory card. 
• 
Execute the sampling trace. The sampling data is saved into the IC memory card. 
• 
Remove the IC memory card. 
 
T3H which is used to display the sampling data stored in the IC memory card: 
• 
Install the IC memory card in which the sampling trace data is stored. 
• 
Set MMR for the PU slot in the I/O allocation in order to use an IC memory card for 
sampling trace function. 
• 
Monitor the sampling trace condition. The condition stored in the IC memory card 
is displayed. 
• 
Display the sampling trace data. The sampling data stored in the IC memory card 
is displayed. 
 
 
 
 
 
 
 
 
 
NOTE
To copy the sampling data stored in the T3H’s file register to an IC memory 
card, set the special device S0620 to ON and display the sampling trace 
condition. By this operation, the sampling trace condition and the sampling 
data stored in file register are copied into the IC memory card.