Toshiba PROSEC T3H Manual De Usuario

Descargar
Página de 73
 
User’s Manual   
31
 
2. Expanded Functions 
 
 
 2.2.3 
Timer 
 
The T3H has 1000 points of timer. 
 
Function type 
Type 
code 
Address range 
Quantity 
Expression 
example 
Timer register 
000 - 999 
1000 words 
T670 
Timer device 
T. 
000 - 999 
1000 points 
T.670 
 
The proportion of the 0.01 s base and the 0.1 s base timers within this 1000 points 
can be specified by user. This setting information is stored in the system information. 
 
10 ms Timer Range Setting: 
 
T000  -  T [       ]   
 
User setting (max. 999) 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 2.2.4 
Link 
register 
 
The T3H has 2048 words of link register. This link register is prepared for the 
TOSLINE-S20 (here called S20). 
 
Function type 
Type 
code 
Address range 
Quantity 
Expression 
example 
Link register 
0000 - 2047 
2048 words 
W1500 
Link device 
0000 - 999F 
16000 points 
Z847E 
 
The link device Z corresponds to a bit in a link register W. The bit access as Z device 
is available for the leading 1000 words of W register. 
 
NOTE
T3H internally, the register ranges T000 to T511 and T512 to T999 are 
handled separately. Therefore, index modification or table designation 
across these ranges are not allowed. 
 
For example) 
 
├─[ T450  TMOV  (100)  D1000 ]- 
Not allowed 
 
 
├─[ T450  TMOV  (62)  D1000 ]- 
Allowed 
│ 
├─[ T512  TMOV  (38)  D1062 ]-