40
G7 ASD Operation Manual
Startup Wizard Requirements
The Startup Wizard queries the user for information on the input and output signal parameters of the 
ASD. The ASD may also be setup by directly accessing each of the control settings via the Program 
menu or the Direct Access Numbers (see the section titled 
).
Upon initial system powerup, the Startup Wizard starts automatically. It may also be run from the 
Program menu after startup if required. The user is queried to either (1) run the Startup Wizard (Run 
Now
), (2) run the Startup Wizard at the next power up, or (3) perform a manual setting of user-selected 
parameters.
If selection (2) is chosen, the system returns to the Program menu and defaults to the Startup Wizard on 
the next power up. If selection (3) is chosen, click the subsequent Finish box and the system returns to the 
Frequency Command screen. If selection (1) (Run Now) is selected, the Startup Wizard will start and 
assist the user with the configuration of the G7 True Torque Control
2
 Adjustable Speed Drive using the 
following user-input screens.
Voltage and Frequency Rating of the Motor
Motors are designed and manufactured for a specific 
voltage and frequency range. The voltage and frequency 
specifications for a given motor may be found on the 
nameplate of the motor.
Upper Limit Frequency
This parameter sets the highest frequency that the G7 will 
accept as a frequency command or frequency setpoint. The 
G7 may output frequencies higher than the Upper Limit 
Frequency
 (but, lower than the Maximum Frequency
when operating in the PID Control mode, Torque Control 
mode, or the Vector Control modes (sensorless or 
feedback).
Lower Limit Frequency
This parameter sets the lowest frequency that the G7 will 
accept as a frequency command or frequency setpoint. The 
G7 will output frequencies lower than the Lower Limit 
Frequency
 when accelerating to the lower limit or 
decelerating to a stop. Frequencies below the Lower Limit 
may be output when operating in the PID Control mode, 
Torque Control mode, or the Vector Control modes 
(sensorless or feedback).