G7 ASD Operation Manual
41
Adjust Accel/Decel Automatically?
When enabled, the G7 adjusts the acceleration and 
deceleration rates according to the applied load. The 
acceleration and deceleration times range from 12.5% to 
800% of the programmed values for the active 
acceleration time [e.g., Acceleration Time #1 (
and Deceleration Time #1 (
)].
The motor and the load must be connected prior to 
selecting Automatic Accel/Decel.
If Automatic Accel/Decel is not enabled, the Acceleration screen will appear followed by the 
Deceleration screen as shown below.
Volts per Hertz Setting
This function establishes the relationship between 
the output frequency and the output voltage.
Settings:
Constant Torque
Variable Torque
Automatic Torque Boost
Sensorless Vector Control (Speed)
Automatic Torque Boost + Automatic Energy Savings
Sensorless Vector Control (Speed) + Automatic Energy Savings
V/f 5-point Setting (Opens 5-point Setting Screen)
Sensorless Vector Control (Speed/Torque Switching)
PG Feedback Vector Control (Speed/Torque Switching)
PG Feedback Vector Control (Speed/Position Switching)
Motor Current Rating
This parameter allows the user to input the full-load 
amperage (FLA) of the motor. This value is used by 
the ASD to determine the Thermal Overload 
protection setting for the motor and may be found 
on the nameplate of the motor.
Acceleration Time
Deceleration Time