GFK-1541B
Chapter 3  Programming Channel Commands
3-41
3
 
Minor Error Codes for Major Error Code 11H (at Remote Server PLC) -
Continued
3111H
Failure to register with backplane driver because the requested task is already
registered.
3211H
Unable to find resource necessary for backplane driver to process a service request.
3311H
Bad sequence number detected in the service request because it is already in use.
3411H
Invalid data detected that prevents backplane driver from completing a request.
3611H
More than the allowable byte length in a single transfer.
4811H
Memory resource problem detected.
4911H
Network buffer resource problem detected.
4C11H
Error detected while attempting to receive mailbox messages from the PLC.
4D11H
Timed out waiting to obtain a backplane transfer buffer.
4E11H
Timed out waiting to transfer a mailbox message to the PLC.
4F11H
Timed out waiting for PLC CPU response.
Minor Error Codes for Major Error Code 90H (at Client PLC)
Error Status
Application Interface Error Description
(Hexadecimal)
0190H
Timeout expired before transfer completed; still waiting on transfer.
0290H
Period expired before transfer completed; still waiting on transfer.
8190H
COMMREQ data block too short for the command.
8290H
COMMREQ data block too short for server PLC node address.
8390H
Invalid server memory type.
8490H
Invalid Program Name.
8590H
Invalid Program Block Name.
8690H
Zero server unit length is not allowed.
8790H
Server unit length is too large.
8890H
Invalid channel number.
8990H
Invalid time unit for period.  (Maximum permitted 3965 hours)
8A90H
Period value is too large.
8B90H
Zero server memory starting address is not allowed.
8C90H
Invalid client memory type.
8D90H
Invalid server host address type.
8E90H
Invalid IP address integer value.  (Must be 0–255)
8F90H
Invalid IP address class.
9090H
Insufficient TCP connection resources to do request.
9190H
Zero local starting address is not allowed.
9290H
Address length value invalid.  Must be 4 for address type.
9390H
COMMREQ data block too short for Program Block name
(including 0 pad).
9490H
COMMREQ data block too short for Program name
(including 0 pad).
9590H
Internal API error.  See PLC Fault Table or exception log for details.  This
problem may occur due to the Ethernet Interface being asked to perform beyond its
capacity.  Try transferring less data per message or establishing fewer
simultaneous connections.