GE GFK-1541B Manual De Usuario

Descargar
Página de 240
3-42
TCP/IP Ethernet Communications for the Series 90™ PLC User's Manual
 
 
 May 2002 
GFK-1541B
3
 
Section 1:   Section 2:   Minor Error Codes for Major Error Code 90H (at Client
PLC) - Continued
9690H
Underlying TCP connection aborted (reset) by server end point.
9790H
Underlying TCP connection aborted by client end point.
9890H
The remote server has no Service Request Processor.
9A90H
Response to session request did not arrive in proper order.
9B90H
Session denied by server PLC.
9C90H
Data response did not arrive in proper order.
9D90H
Data response had unexpected size.
9E90H
Unrecognized COMMREQ command code.
A190H
Invalid CRS word memory type.
A290H
Failed an attempt to update the CRS word.
A490H
Address length value invalid.  Must be 32 for Network Address name type.
B090H
Network Address name length error.  The name cannot exceed 31 ASCII
characters and must be terminated with a NUL character (zero).
B190H
Specified Network Address name could not be resolved into an IP address.
B390H
Internal name resolution error.  See PLC Fault Table or exception log for
details.
B590H
The channel the application is trying to access is owned by a different
protocol.