Chapter 5 Parameters|VFD-S Series 
5-54
 
Revision August 2008, SE09, SW V2.61
 
 
6-03 
Over-Torque Detection Mode (OL2) 
 
 
 
Factory Setting: d0
 
Settings 
d0 
Over-Torque detection disabled. 
 
 
d1 
Enabled during constant speed operation. After the over-torque is 
detected, keep running until OL1 or OL occurs. 
 
 
d2 
Enabled during constant speed operation. After the over-torque is 
detected, stop running. 
 
 
d3 
Over-Torque detection enabled during running, and continues to run 
till OL1 or OL. 
 
 
d4 
Enabled during running. After the over-torque is detected, stop 
running. 
 
6-04 
Over-Torque Detection Level 
Unit: 1
 
Settings 
d30 to d200% 
Factory Setting: d150
 
This setting is proportional to the Rated Output Current of the drive.
 
 
6-05 
Over-Torque Detection Time 
Unit: 0.1
 
Settings 
d0.1 to d10.0 sec 
Factory Setting: d0.1
 
If a Multi-Function Output Terminal is set as Over-Torque Detection Indication and the output 
current exceeds the Over-Torque Detection Level (Pr.6-04, Factory Setting: 150%), the Over-
Torque Detection Time (Pr.6-05, Factory setting: 0.1) and the setting of multi-function terminal 
is Over-Torque Detection Indication, the contact will be “close”.  
 
 
6-06 
Electronic Thermal Overload Relay Selection 
 
 
 
Factory Setting: d2
 
Settings 
Operate with a Standard Motor (self-cooled by fan) 
 
 
Operate with a Special Motor (forced external cooling) 
  
Operation 
disabled 
 
This function is used to protect the motor from overloading or overheating.
 
 
6-07 
Electronic Thermal Characteristic 
 
Unit: 1
 
Settings 
d30 to d600Sec 
Factory Setting: d60
 
The parameter determines the time required activating the I
2
t electronic thermal protection 
function. The graph below shows I
2
t curves for 150% output power for 1 minute.